Troubleshooting
Serial commu-
Indicator
nications
status
mode
Host Link,
The COMM@
slave-initiated
indicators are
communica-
flashing, but
tions
there is no
response from
the host.
126
Status
I/O memory
information,
etc.
A transmis-
---
sion error has
not been
detected at
the host.
---
---
---
Communications
parameters and
baud rate settings in
the PC Setup do not
correspond with the
settings at the host.
Cause
There is a hard-
Conduct a loopback test in
ware error in the
serial communications
reception circuit.
mode to check the trans-
mission lines. If an error
occurs during the test,
replace the Serial Commu-
nications Board.
Cables are incor-
Check the wiring and cor-
rectly wired.
rect.
There is a hard-
Conduct a loopback test in
ware error in the
serial communications
reception circuit.
mode to check the trans-
mission lines. If an error
Adapters such as
occurs during the test,
the NT-AL001-E are
replace the Serial Commu-
incorrectly wired or
nications Board.
set.
---
Check the program at the
host. When unsolicited
communications are used
with Host Link mode, there
must be a response
returned from the host for
every command sent from
the Serial Communica-
tions Board.
The communica-
Reset the parameters in
tions conditions and
the PC Setup and at the
baud rate do not
host correctly.
match the settings
at the host.
Section 9-2
Remedy