Omron CQM1H-SCB41 Operation Manual page 406

Sysmac cqm1h series serial communications board
Hide thumbs Also See for CQM1H-SCB41:
Table of Contents

Advertisement

V600/V620 ID Controller Protocol
Write (Hexadecimal/1) (Sequence No. 522)
This sequence is used when the number of Heads to be written to the Carrier is 1.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
data
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note 1. Data of which Data Carrier designated for hexadecimal is sent beginning with the largest offset from
the send data words.
2. Always set an even number of digits for the write data.
+0
Number of send data words
(Undefined)
+1
(Undefined)
+2
Leading address No.
+3
Number of write digits
+4
Write data
+5
~
Max +35
(Undefined)
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Relevant Unit No. (2 digits BCD)
+2
R/W Head CH No. (1 digit BCD)
+3
Leading address No.
(4 digits Hexadecimal)
+4
Number of write digits
(4 digits BCD)
+5 to
Write data (Hexadecimal)
35
Unit No.
Head CH No.
~
Write data
0006 to 0036
00 to 07 (CD1D)
00 to 15 (CA2A)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF
0002 to 0122
Input in hexadecimal
Up to 122 digits (max.)
Appendix M
Data
391