Omron CQM1H-SCB41 Operation Manual page 218

Sysmac cqm1h series serial communications board
Hide thumbs Also See for CQM1H-SCB41:
Table of Contents

Advertisement

E5ZE Temperature Controller Read Protocol
Read Manual Reset Value (Sequence No. 114)
Reads the manual reset value and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Read Ramp Value (Sequence No. 115)
Reads the ramp values and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Offset
Contents (data format)
+0
Number of receive data words
(4 digits BCD)
+1
Channel 0
Input shift value (4 digits BCD)
+2
Channel 1
Input shift value (4 digits BCD)
+8
Channel 7
Input shift value (4 digits BCD)
Number of send data words
+0
(Undefined)
+1
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Unit No. (2 digits Hex)
Number of receive data words
+0
Manual reset value
+1
Manual reset value
+2
~
Manual reset value
+8
Offset
Contents (data format)
+0
Number of receive data words
(4 digits BCD)
+1
Channel 0
Manual reset value
(4 digits BCD)
+2
Channel 1
Manual reset value
(4 digits BCD)
+8
Channel 7
Manual reset value
(4 digits BCD)
Number of send data words
+0
+1
(Undefined)
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Unit No. (2 digits Hex)
0009
0000 to 0999
F indicates a negative number.
0000 to 0999
F indicates a negative number.
0000 to 0999
F indicates a negative number.
Unit No.
0002 (fixed)
00 to 0F
Channel 0
Channel 1
~
Channel 7
0009
0000 to 1000
0000 to 1000
0000 to 1000
Unit No.
0002 (fixed)
00 to 0F
Appendix E
Data
Data
Data
Data
203

Advertisement

Table of Contents
loading