E5ZE Temperature Controller Read Protocol
Read Proportional Band, Integral Time, and Derivative Time
(Sequence No. 104)
Reads the proportional bands (constant P), integral times (constant I), and derivative times (Constant D) and
stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Read Control Period (Sequence No. 105)
Reads the control periods and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
+0
Number of send data words
(Undefined)
+1
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Unit No. (2 digits Hex)
+0
Number of receive data words
+1
Constant P
+2
Constant I
+3
Constant D
~
+22
Constant P
+23
Constant I
+24
Constant D
Offset
Contents (data format)
+0
Number of receive data words
(4 digits BCD)
+1
Channel 0
Constant P (4 digits BCD)
+2
Channel 0
Constant I (4 digits BCD)
+3
Channel 0
Constant D (4 digits BCD)
+22
Channel 7
Constant P (4 digits BCD)
+2 3
Channel 7
Constant I (4 digits BCD)
+24
Channel 7
Constant D (4 digits BCD)
Number of send data words
+0
(Undefined)
+1
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Unit No. (2 digits Hex)
Unit No.
0002 (fixed)
00 to 0F
Channel 0
~
Channel 7
0025
0000 to 9999
0000 to 3999
0000 to 3999
•
•
•
0000 to 9999
0000 to 3999
0000 to 3999
Unit No.
0002 (fixed)
00 to 0F
Appendix E
Data
Data
Data
197