Error code
Classification
(hexadecimal)
*1
2011H
Moderate
*2
2210H
Moderate
*2
2220H
Moderate
*2
2400H
Moderate
*1
301H
Moderate
Error name
Description and cause
Non-volatile
The IP address and subnet mask stored in
memory data error
the non-volatile memory are abnormal.
(IP address)
Synchronous
When CC-Link IE TSN Network
communication
synchronous communication function is
error 1
used, time synchronization is abnormal.
Synchronous
When CC-Link IE TSN Network
communication
synchronous communication function is
error 2
used, synchronous communication with the
master station has failed for a certain
period of time.
IP address/station
The IP address/station number setting
number setting
switches are set to 255.
switches out of
range error (IP
address)
Filter sampling
Set Filter sampling pulse (B) (FPGA
pulse (B) setting
register address: 1000_2000H to
error
1000_2004H) is invalid.
■For DC input
A value other than Data sampling timing
(FH) is set for Filter sampling pulse (B).
■For differential input
• Data sampling timing (FH) is set for Filter
sampling pulse (B).
• A value set for Filter sampling pulse
(B) is different from a value set for
Data sampling timing (B).
Action
• The module will be automatically
recovered immediately after the error
occurs. However, the stored IP address
and subnet mask are lost, and operation
is performed assuming that the following
are stored.
IP Address: 192.168.3.250
Subnet mask: 255.255.255.0
• Take measures against noise with a
shielded cable for connection.
• If this error occurs again, the possible
cause is a module failure. Please consult
your local Mitsubishi representative.
• Check that the system configuration
meets the specifications by referring to
the manual for the master station.
• Check that no communication error has
occurred on the other stations.
• Check that no remote reset has been
performed to the other stations.
• Take measures against noise on the
transmission path.
• If this error occurs again, the possible
cause is a module failure. Please consult
your local Mitsubishi representative.
• Set a longer time for the synchronization
cycle of the master station.
• Reduce the number of remote stations
that operate with the CC-Link IE TSN
Network synchronous communication
function.
• Take measures against noise on the
transmission path.
• If this error occurs again, the possible
cause is a module failure. Please consult
your local Mitsubishi representative.
Turn on the power supply with the IP
address/station number setting switches
set to a value in the range 0 to 254.
■For DC input
Set Filter sampling pulse (B) (FPGA
register address: 1000_2000H to
1000_2004H) to Data sampling timing
(FH).
■For differential input
• Set Filter sampling pulse (B) (FPGA
register address: 1000_2000H to
1000_2004H) to a value within 0.01s
(0H) to 100.00s (EH).
• Set the same value for both Filter
sampling pulse (B) and Data sampling
timing (B).
24 ERROR CODE LIST