Mitsubishi Electric NZ2GN2S-D41P01 User Manual page 477

Cc-link ie tsn fpga module
Table of Contents

Advertisement

Logging control suspension flag
■Device number
Name
Logging control suspension flag
■Description
Use as an interlock to turn on and off the logging control suspend request (RY7) used to stop the logging data collection or
FTP transfer.
This signal turns on under the following conditions.
• When Logging operation status monitor (RWrB) is Collecting (2H) or Collecting after trigger (3H), if Logging control
suspend request (RY7) is turned on, this signal turns on and Logging operation status monitor (RWrB) becomes Collection
start waiting (1H).
• This signal turns on when the logging control suspend request (RY7) is turned on while the Logging operation status
monitor (RWrB) is FTP transferring (4H). Depending on the ON/OFF state of FTP resend allowed (RY4), the Logging
operation status monitor (RWrB) becomes FTP transfer start waiting (5H) when FTP resend allowed (RY4) is ON, and
becomes Collection start waiting (1H) when FTP resend allowed (RY4) is OFF.
This signal turns off when Logging control suspend request (RY7) is turned off.
■2H: Collecting or 3H: Collecting after trigger
ON
FPGA controlling flag
(RX0)
Logging control stop flag
OFF
(RX7)
Logging control stop request
OFF
(RY7)
Logging operation state
monitor (RWrB)
Performed by FPGA module
Executed by the program
(1) Collecting (2H) / Collecting after trigger (3H)
(2) Collection start waiting (1H)
■4H: FTP transfer
ON
FTP resend allowed
(RY4)
Logging control stop flag
OFF
(RX7)
Logging control stop request
OFF
(RY7)
Logging operation state
monitor (RWrB)
Performed by FPGA module
Executed by the program
(1) FTP transferring (4H)
(2) FTP transfer start waiting (5H)
Device number
RX7
ON
ON
(1)
ON
ON
(1)
(2)
(2)
Appendix 1 Remote I/O Signal