Mitsubishi Electric NZ2GN2S-D41P01 User Manual page 462

Cc-link ie tsn fpga module
Table of Contents

Advertisement

Error code
Classification
(hexadecimal)
3C00H
Major
*2
3C01H
Major
*2
3C02H
Major
3C03H
Major
*1 The error can be cleared by turning on and off Error clear request flag (RYA).
*2 The error cannot be cleared by turning on and off Error clear request flag (RYA). After eliminating the cause of the error, turn off and on
the power supply or perform a remote reset.
24 ERROR CODE LIST
460
Error name
Description and cause
Hardware error
Module hardware error
FPGA configuration
■During FPGA configuration
error
FPGA configuration was not completed
properly because of the following reasons.
• Invalid configuration data is written to the
configuration ROM.
• Data in the configuration ROM is deleted.
• During configuration data transfer, an
error occurred due to noise.
• Configuration data was written via JTAG
while the function setting switch 5 was
off.
■After FPGA configuration is complete
An error was detected by FPGA
configuration state monitor.
Extension module
An extension module is not properly
mounting state error
mounted.
Hardware error
Module hardware error
Action
• Power off and on the module power
supply.
• If this error occurs again, the possible
cause is a module failure. Please consult
your local Mitsubishi representative.
• Power off and on the module power
supply.
• Write configuration data to the
configuration ROM again, and then turn
off and on the module power supply.
• Take measures to reduce noise, such as
the use of shielded cables for external
input/output signal connections.
• Be sure that the function setting switch 5
is on while configuration data is being
written via JTAG.
• If this error occurs again after the
measures above are taken, the possible
cause is a module failure. Please consult
your local Mitsubishi representative.
• Turn off the module power supply, and
check the mounting state of the
extension module. Then, turn on the
module power supply.
• When the extension module is properly
mounted, the possible cause is noise
effects. Take measures to reduce noise.
• If this error occurs again after the
measures above are taken, the possible
cause is a module failure. Please consult
your local Mitsubishi representative.
• Check whether the standard circuit was
changed during FPGA internal circuit
development.
• Power off and on the module power
supply.
• If this error occurs again, the possible
cause is a module failure. Please consult
your local Mitsubishi representative.

Advertisement

Table of Contents
loading