Remote Output Signals - Mitsubishi Electric NZ2GFCE-60DAV8 User Manual

Cc-link ie field network digital-analog converter module (e-con type)
Table of Contents

Advertisement

Remote output signals

Initial data setting request flag
■Device number
Signal name
Initial data setting request flag
■Description
Turn on Initial data setting request flag (RY9) after writing parameter data to the remote buffer memory using the program.
Upon completion of the change of operating conditions, Initial data setting completed flag (RX9) turns on.
For the timing of when to turn on and off, refer to the following:
Page 102 Initial data setting completed flag
Error clear request flag
■Device number
Signal name
Error clear request flag
■Description
Error clear request flag (RYA) is used to clear Error flag (RXA) and Latest error code (RWr0).
■When a moderate error occurs
Eliminating the cause of the error and turning off and on Error clear request flag (RYA) allow the error status to be cleared,
resulting in Error flag (RXA) turning off.
Before Error flag (RXA) turns off, turning on and off Error clear request flag (RYA) does not allow Error flag (RXA) to turn off.
For the timing of when to turn on and off, refer to the following:
Page 103 Error flag
■When a major error occurs
Error flag (RXA) does not turn off even by turning on and off Error clear request flag (RYA).
For the timing of turning the flag on and off, refer to the following.
Page 103 Error flag
Downloaded from
ManualsNet.com
search engine
Device number
RY9
Device number
RYA