Query Format
Description
Returned Data Format
Query Example
Command Syntax
Description
Parameters
Parameter Format
Example
Query Format
Returned Data Format
Query Example
Query Format
Description
Returned Data Format
Query Example
8.7.4
Current Programming Commands
Command Syntax
Description
Parameters
Parameter Format
Example
Query Format
Returned Data Format
Query Example
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
ADF Series Power Source Operation Manual
[SOURce:]FREQuency:LIMit:RANGe?
This command returns the lower and upper frequency user limit set
value.s
<nr2>, <nr2>
FREQ:LIM:RANG?
53.0000,63.0000
[SOURce:]FREQuency:SLEW
Sets the frequency slew rate in Hz/msec.
0.01 – 1200.00
<nr2>
FREQ:SLEW 100.0
[SOURce:]FREQuency:SLEW?
<nr2>
FREQ:SLEW?
100.0000
[SOURce:]FREQuency:SPAN?
This command is provided to support backward compatibility with
Pacific Power UPC controllers. Refer also to the
"SYSTem:COMPatible" command. For ADF Series®, this query always
returns 1200.0000
<nr2>
FREQ:SPAN?
1200.0000
[SOURce:]CURRent:LIMit#
This command sets the programmable current level for the selected
phase #. If # is omitted, sets all phases to current level specified. The
value set cannot exceed the maximum current capability of the
power source as returned by the "[SOURce:]CURRent:LIMit#:MAX?"
command.
If the load current exceeds the current limit set point, the source will
go into constant current mode to maintain the load current at the set
limit level.
0.00 – MAX
<nr2>
CURR:LIM 20.5
[SOURce:]CURRent:LIMit#?
<nr2>
CURR:LIM?
41.667,41.667,41.667
ADF SERIES™ OPERATION MANUAL
Remote Control Programming
SECTION 8:
Page 207 of 349