Pacific Power Source ADF Series Operation Manual page 202

Table of Contents

Advertisement

Command Syntax
Description
VOLT:INIT? = ON
VOLT:INIT? = OFF
Parameters
Parameter Format
Example
Query Format
Returned Data Format
Query Example
Command Syntax
Description
Parameters
Parameter Format
Example
Query Format
Returned Data Format
Query Example
Commands available only with Option D:
Command Syntax
Description
Parameters
Parameter Format
Example
Query Format
Returned Data Format
Query Example
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
ADF Series Power Source Operation Manual
[SOURce:]VOLTage[:AC]:INITial
This command is equivalent to the "[SOURce:]INITial <n>" command
but applies only to the AC1, AC2 and AC3 parameters.
Set points of the unit at power on will be the last set after power off.
The set points affected by this command are:
- Voltage AC1
- Voltage AC2
- Voltage AC3
Set points of the unit at power on will have a default value of:
- Voltage AC1 = 0V
- Voltage AC2 = 0V
- Voltage AC3 = 0V
< 0 | OFF | 1 | ON >
<b>
VOLT:AC:INIT OFF
[SOURce:]VOLTage[:AC]:INITial?
<b>
VOLT:AC:INIT?
0
[SOURce:]VOLTage:EXTend
Available only on ADF models with Option V.
This command grants access to a higher voltage range extension
mode. When enabled, AC voltage settings up to 333V L-N are
supported.
[ 0 | OFF | 1 | 2 ]
0 = Off, 312Vac max.
1 = 320Vac max
2 = 333Vac max
<bool>
VOLT:EXT 1
[SOURce:]VOLTage:EXTend?
<nr1>
VOLT:EXT?
1
[SOURce:]VOLTage:DC#
Sets DC voltage for phase #. If # is omitted, sets all available phases to
value specified.
Note: Source must be in DC or AC+DC mode and UPC compatibility
mode must be disabled.
Range 0.0000 - 425.0000
<nr2>
VOLT:DC1 375.0
[SOURce:]VOLTage:DC#?
<nr2>
VOLT:DC1?
375.0000
ADF SERIES™ OPERATION MANUAL