ADF Series Power Source Operation Manual
MEASure:ALL#?
Returns 14 parametric measurements for the selected phase # as a
comma delimited string. The # is used to specify phase A, B or C using
1, 2 or 3 respectively. If phase reference is omitted, measurement
data for all three phases is returned. Value order for each phase is:
1. Frequency (repeats for each phase)
2. VLL AC+DC
3. VLL AC RMS
4. 0
5. VLN AC+DC
6. VLN AC
7. 0
8. I AC
9. I DC
10. POWER
11. APP POWER
12. I PEAK
13. PF
14. CF
Thus, each phase data set consists of 14 values. For all phases, a total
of 42 comma separated values are returned.
<nr2>,<nr2>,....,<nr2>,<nr2>
MEAS:ALL1?
1200.0000,519.5981,519.5981,0.0028,299.9990,299.9989,-
0.0007,0.1711,-0.0016,0.0000,0.0513,0.4849,0.0000,0.0000
MEASure:LOGger:START
Starts the logging of measurements process. The process consists of
taking measurements and saving them in a file. The log file can be
found in the "datalogger" folder and is a comma separated value
format (.csv) file. Measurements will be taken while the output is
enabled only.
None
n/a
MEAS:LOG:START
None
MEASure:LOGger:STOP
Stops the logging process that was started with
MEASure:LOGger:START.
None
n/a
MEAS:LOG:STOP
None