476 Parameters
No.
Name/Value
93.23
Maximum pulse
waiting time
93.24
Pulse edge filtering
93.25
Pulse
overfrequency
function
93.30
Serial link mode
93.31
EnDat calc time
93.32
SSI cycle time
93.33
SSI clock cycles
93.34
SSI position msb
93.35
SSI revolution msb
93.36
SSI data format
93.37
SSI baud rate
93.40
SSI zero phase
93.45
Hiperface parity
93.46
Hiperface baud rate
93.47
Hiperface node
address
95

95 HW configuration

95.01
Supply voltage
Not given
208...240 V
380...415 V
Description
(Visible when parameter
HTL)
See parameter
92.23 Maximum pulse waiting
(Visible when parameter
See parameter
92.24 Pulse edge
(Visible when parameter
See parameter
92.25 Pulse overfrequency
(Visible when an absolute encoder is selected)
See parameter
92.30 Serial link
(Visible when an absolute encoder is selected)
See parameter
92.31 EnDat max calculation
(Visible when an absolute encoder is selected)
See parameter
92.32 SSI cycle
(Visible when an absolute encoder is selected)
See parameter
92.33 SSI clock
(Visible when an absolute encoder is selected)
See parameter
92.34 SSI position
(Visible when an absolute encoder is selected)
See parameter
92.35 SSI revolution
(Visible when an absolute encoder is selected)
See parameter
92.36 SSI data
(Visible when an absolute encoder is selected)
See parameter
92.37 SSI baud
(Visible when an absolute encoder is selected)
See parameter
92.40 SSI zero
(Visible when an absolute encoder is selected)
See parameter
92.45 Hiperface
(Visible when an absolute encoder is selected)
See parameter
92.46 Hiperface baud
(Visible when an absolute encoder is selected)
See parameter
92.47 Hiperface node
Various hardware-related settings.
Selects the supply voltage range. This parameter is used by
the drive to determine the nominal voltage of the supply
network. The parameter also affects the current ratings and
the DC voltage control functions (trip and brake chopper
activation limits) of the drive.
WARNING! An incorrect setting may cause the
motor to rush uncontrollably, or the brake chopper or
resistor to overload.
Note: The selections shown depend on the hardware of the
drive. If only one voltage range is valid for the drive in
question, it is selected by default.
No voltage range selected. The drive will not start
modulating before a range is selected.
208...240 V
380...415 V
93.01 Encoder 2 type
=
time.
93.01 Encoder 2 type
= HTL)
filtering.
93.01 Encoder 2 type
= HTL)
function.
mode.
time.
time.
cycles.
msb.
msb.
format.
rate.
phase.
parity.
rate.
address.
Def/FbEq16
TTL
or
4 ms
No filtering
Fault
Initial
position
50 ms
100 us
2
1
1
Binary
100 kBit/s
315-45 deg
Odd
4800 bits/s
64
-
0
1
2

Hide quick links: