99 Motor data

99.03
Motor type
Asynchronous
motor
Permanent magnet
motor
SynRM
99.04
Motor control mode
DTC
Scalar
99.06
Motor nominal
current
0.0 ... 6400.0 A
Description
Motor configuration settings.
Selects the motor type.
Note: This parameter cannot be changed while the drive is
running.
Standard squirrel cage AC induction motor (asynchronous
induction motor).
Permanent magnet motor. Three-phase AC synchronous
motor with permanent magnet rotor and sinusoidal
BackEMF voltage.
Synchronous reluctance motor. Three-phase AC
synchronous motor with salient pole rotor without permanent
magnets.
Selects the motor control mode.
Direct torque control. This mode is suitable for most
applications.
Note: Instead of direct torque control, scalar control is also
available, and should be used in the following situations:
• with multi-motor applications 1) if the load is not equally
shared between the motors, 2) if the motors are of
different sizes, or 3) if the motors are going to be changed
after the motor identification (ID run)
• if the nominal current of the motor is less than 1/6 of the
nominal output current of the drive
• if the drive is used with no motor connected (for example,
for test purposes).
See also section
Operating modes of the drive
Scalar control. The outstanding motor control accuracy of
DTC cannot be achieved in scalar control.
Refer to the
DTC
selection above for a list of applications
where scalar control should definitely be used.
Notes:
• Correct motor operation requires that the magnetizing
current of the motor does not exceed 90% of the nominal
current of the inverter.
• Some standard features are disabled in scalar control
mode.
See also section
Scalar motor control
control), and section
Operating modes of the drive
(page 43).
Defines the nominal motor current. This setting must match
the value on the rating plate of the motor. If multiple motors
are connected to the drive, enter the total current of the
motors.
Notes:
• Correct motor operation requires that the magnetizing
current of the motor does not exceed 90% of the nominal
current of the drive.
• This parameter cannot be changed while the drive is
running.
Nominal current of the motor. The allowable range is
1/6...2 × I
(nominal current) of the drive (0...2 × I
N
scalar control mode).
(page 43).
(page
Scalar motor
with
N
Def/FbEq16
Asynchro-
nous
motor,
SynRM
(95.21
b1)
0
1
2
DTC
0
1
0.0 A
1 = 1 A