ABB ACS880 Firmware Manual page 583

Industrial drives, winder control program, option +n5000
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

Code
Warning
(hex)
A8BF
ULC underload
warning
Programmable fault:
37.04 ULC underload
actions
A8C0
Fan service counter
A981
External warning 1
(Editable message text)
Programmable warning:
31.01 External event 1
source
31.02 External event 1
type
A982
External warning 2
(Editable message text)
Programmable warning:
31.03 External event 2
source
31.04 External event 2
type
A983
External warning 3
(Editable message text)
Programmable warning:
31.05 External event 3
source
31.06 External event 3
type
A984
External warning 4
(Editable message text)
Programmable warning:
31.07 External event 4
source
31.08 External event 4
type
A985
External warning 5
(Editable message text)
Programmable warning:
31.09 External event 5
source
31.10 External event 5
type
AF85
Line side unit warning
AF8C
Process PID sleep
mode
Cause
Selected signal has fallen
below the user underload
curve.
A cooling fan has reached the
end of its estimated lifetime.
See parameters
05.41
and
05.42.
Fault in external device 1.
Fault in external device 2.
Fault in external device 3.
Fault in external device 4.
Fault in external device 5.
The supply unit (or other
converter) has generated a
warning.
The drive is entering sleep
mode.
Fault tracing 583
What to do
Check for any operating conditions
decreasing the monitored signal (for
example, loss of load if the torque or
current is being monitored).
Check the definition of the load curve
(parameter group
37 User load
Check the auxiliary code. The code
indicates which fan is to be replaced.
0: Main cooling fan
1: Auxiliary cooling fan
2: Auxiliary cooling fan 2
3: Cabinet cooling fan
4: PCB compartment fan
Refer to the hardware manual of the
drive for fan replacement instructions.
Check the external device.
Check setting of parameter
External event 1
source.
Check the external device.
Check setting of parameter
External event 2
source.
Check the external device.
Check setting of parameter
External event 3
source.
Check the external device.
Check setting of parameter
External event 4
source.
Check the external device.
Check setting of parameter
External event 5
source.
The auxiliary code specifies the original
warning code in the supply unit control
program. Refer to the firmware manual of
the supply unit.
Informative warning. See section
function for process PID control
107), and parameters 40.41...40.48.
curve).
31.01
31.03
31.05
31.07