394 Parameters
No.
Name/Value
58.104 Data I/O 4
58.105 Data I/O 5
58.106 Data I/O 6
58.107 Data I/O 7
...
...
58.124 Data I/O 24
60
60 DDCS
communication
60.01
M/F communication
port
Not in use
Slot 1A
Slot 2A
Slot 3A
Slot 1B
Slot 2B
Slot 3B
XD2D
RDCO CH 2
Description
Defines the address in the drive which the Modbus master
accesses when it reads from or writes to register address
400004.
For the selections, see parameter
Defines the address in the drive which the Modbus master
accesses when it reads from or writes to register address
400005.
For the selections, see parameter
Defines the address in the drive which the Modbus master
accesses when it reads from or writes to register address
400006.
For the selections, see parameter
Parameter selector for Modbus register address 400007.
For the selections, see parameter
...
Parameter selector for Modbus register address 400024.
For the selections, see parameter
DDCS communication configuration.
The DDCS protocol is used in the communication between
• drives in a master/follower configuration (see page 74),
• the drive and an external controller such as the AC 800M
(see page 81), or
All of the above utilize a fiber optic link which also requires
an FDCO module (with ZCU control units) or an RDCO
module (with BCU control units). Master/follower and
external controller communication can also be implemented
through twisted-pair cable connected to the XD2D connector
of the drive.
Selects the connection used by the master/follower
functionality.
None (communication disabled).
Channel A on FDCO module in slot 1 (with ZCU control unit
only).
Channel A on FDCO module in slot 2 (with ZCU control unit
only).
Channel A on FDCO module in slot 3 (with ZCU control unit
only).
Channel B on FDCO module in slot 1 (with ZCU control unit
only).
Channel B on FDCO module in slot 2 (with ZCU control unit
only).
Channel B on FDCO module in slot 3 (with ZCU control unit
only).
Connector XD2D.
Channel 2 on RDCO module (with BCU control unit only).
58.101 Data I/O
1.
58.101 Data I/O
1.
58.101 Data I/O
1.
58.101 Data I/O
1.
58.101 Data I/O
1.
Def/FbEq16
SW 16bit
Act1 16bit
Act2 16bit
None
...
None
Not in use
0
1
2
3
4
5
6
7
12