ABB ACS880 Firmware Manual page 162

Industrial drives, winder control program, option +n5000
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

162 Parameters
No.
Name/Value
04.17
2nd latest warning
0000h...FFFFh
04.18
3rd latest warning
0000h...FFFFh
04.19
4th latest warning
0000h...FFFFh
04.20
5th latest warning
0000h...FFFFh
04.21
Fault word 1
(04.120
Bit
Standard ctrl
program)
0
SHORT CIRC
1
OVERCURRENT
2
DC OVERVOLT
3
ACS800 TEMP
4
EARTH FAULT
5
THERMISTOR
6
MOTOR TEMP
7
SYSTEM_FAULT
8
UNDERLOAD
9
OVERFREQ
10
Reserved
11
Reserved
12
Reserved
13
Reserved
14
Reserved
15
Reserved
0000h...FFFFh
Description
Code of the 2nd stored (non-active) warning.
2nd stored warning.
Code of the 3rd stored (non-active) warning.
3rd stored warning.
Code of the 4th stored (non-active) warning.
4th stored warning.
Code of the 5th stored (non-active) warning.
5th stored warning.
ACS800-compatible fault word 1.
The bit assignments of this word correspond to FAULT
WORD 1 in the ACS800. Parameter
word compatibility
determines whether the bit assignments
are according to the ACS800 Standard or ACS800 System
control program.
Each may indicate several ACS880 events as listed below.
This parameter is read-only.
ACS800 fault name
=
ACS800
(04.120
=
ACS800
System ctrl
program)
SHORT CIRC
OVERCURRENT
DC OVERVOLT
ACS800 TEMP
EARTH FAULT
MOTOR TEMP M
MOTOR TEMP
SYSTEM_FAULT
UNDERLOAD
OVERFREQ
MPROT SWITCH
CH2 COMM LOSS
SC (INU1)
SC (INU2)
SC (INU3)
SC (INU4)
ACS800-compatible fault word 1.
04.120 Fault/Warning
ACS880 events indicated by this bit
(see
Fault
tracing, page 565)
2340
2310
3210
2381, 4210, 4290, 42F1, 4310,
2330, 2392,
3181
4981
4982
6481, 6487, 64A1, 64A2, 64A3, 64B1, 64E1,
6881, 6882, 6883,
6885
-
7310
9081
7582
2340
(XXYY YY01)
2340
(XXYY YY02)
2340
(XXYY YY03)
2340
(XXYY YY04)
Def/FbEq16
-
1 = 1
-
1 = 1
-
1 = 1
-
1 = 1
-
4380
1 = 1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents