Process Pid Set 1 - ABB ACS880 Firmware Manual

Industrial drives, winder control program, option +n5000
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
37.41
ULC overload timer
0.0 ... 10000.0 s
37.42
ULC underload
timer
0.0 ... 10000.0 s

40 Process PID set 1

40.01
Process PID output
actual
-32768.00 ...
32767.00
40.02
Process PID
feedback actual
-32768.00 ...
32767.00
40.03
Process PID
setpoint actual
-32768.00 ...
32767.00
40.04
Process PID
deviation actual
-32768.00 ...
32767.00
Description
Defines the time for which the monitored signal must
continuously stay above the overload curve before the drive
takes the action selected by
Overload timer.
Defines the time for which the monitored signal must
continuously stay below the underload curve before the
drive takes the action selected by
actions.
Underload timer.
Parameter values for process PID control.
The drive contains a single active PID controller for process
use, however two separate complete set-ups can be
programmed and stored.
The first set is made up of parameters 40.07...40.56*, the
second set is defined by the parameters in group
PID set
2. The binary source that defines which set is used
is selected by parameter
See also the control chain diagrams on pages
*The remaining parameters in this group are common for
both sets.
Displays the output of the process PID controller. See the
control chain diagram on page 659.
This parameter is read-only. The unit is selected by
parameter
40.12 Set 1 unit
Process PID controller output.
Displays the value of process feedback after source
selection, mathematical function (parameter
feedback
function), and filtering. See the control chain
diagram on page 658.
This parameter is read-only. The unit is selected by
parameter
40.12 Set 1 unit
Process feedback.
Displays the value of process PID setpoint after source
selection, mathematical function
function), limitation and ramping. See the control chain
diagram on page 659.
This parameter is read-only. The unit is selected by
parameter
40.12 Set 1 unit
Setpoint for process PID controller.
Displays the process PID deviation. By default, this value
equals setpoint - feedback, but deviation can be inverted by
parameter
40.31 Set 1 deviation
chain diagram on page 659.
This parameter is read-only. The unit is selected by
parameter
40.12 Set 1 unit
PID deviation.
37.03 ULC overload
37.04 ULC underload
41 Process
40.57 PID set1/set2
selection.
658
selection.
40.10 Set 1
selection.
(40.18 Set 1 setpoint
selection.
inversion. See the control
selection.
Parameters 341
Def/FbEq16
20.0 s
actions.
1 = 1 s
20.0 s
1 = 1 s
and 659.
-
1 = 1 unit
-
1 = 1 unit
-
1 = 1 unit
-
1 = 1 unit