ABB ACS880 Firmware Manual page 297

Industrial drives, winder control program, option +n5000
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
30.12
Maximum speed
-30000.00 ...
30000.00 rpm
30.13
Minimum frequency
-500.00 ...
500.00 Hz
30.14
Maximum frequency
-500.00 ...
500.00 Hz
30.15
Maximum start
current enable
Disable
Enable
30.16
Maximum start
current
0.00 ... 30000.00 A
30.17
Maximum current
0.00 ... 30000.00 A
Description
Defines the maximum allowed speed.
WARNING! This value must not be lower than
Minimum
speed.
WARNING! In frequency control mode, this limit is
not effective. Make sure the frequency limits
and 30.14) are set appropriately if frequency control
is used.
WARNING! In a master/follower configuration, do not
set maximum and minimum speed limits with the
same sign on a follower drive. See section
Master/follower functionality
Maximum speed.
Defines the minimum allowed frequency.
WARNING! This value must not be higher than
Maximum
frequency.
WARNING! This limit is effective in frequency control
mode only.
Minimum frequency.
Defines the maximum allowed frequency.
WARNING! This value must not be lower than
Minimum
frequency.
WARNING! This limit is effective in frequency control
mode only.
Maximum frequency.
A temporary motor current limit specifically for starting can
be defined by this parameter and
current.
When this parameter is set to Enable, the drive observes the
start current limit defined by
The limit is in force for 2 seconds after initial magnetization
(of an asynchronous induction motor) or autophasing (of a
permanent magnet motor), but not more often than once in
every 7 seconds. Otherwise, the limit defined by
Maximum current
is in force.
Note: The availability of a start current higher than the
general limit depends on drive hardware.
Start current limit disabled.
Start current limit enabled.
Defines a maximum start current when enabled by
parameter
30.15 Maximum start current
Maximum start current.
Defines the maximum allowed motor current.
Maximum motor current.
(page 74).
30.16 Maximum start
30.16 Maximum start
current.
30.17
enable.
Parameters 297
Def/FbEq16
1500.00 rpm;
-1800.00 rpm
30.11
(95.20
b0)
(30.13
See par.
46.01
-50.00 Hz;
-60.00 Hz
30.14
(95.20
b0)
See par.
46.02
-50.00 Hz;
-60.00 Hz
30.13
(95.20
b0)
See par.
46.02
Disable
0
1
-
1 = 1 A
0.00 A
1 = 1 A

Hide quick links: