322 Parameters
No.
Name/Value
33.61
Value counter 2
warn limit
-2147483008 ...
2147483008
33.62
Value counter 2
function
Bit
Function
0
Counter mode
0 = Loop: When the limit is reached, the counter is reset. The counter status (bit 5 of
33.01) switches to 1 for one second. The warning (if enabled) stays active for at least
10 seconds.
1 = Saturate: When the limit is reached, the counter status (bit 5 of 33.01) switches to
1, and remains so until
33.60
1
Warning enable
0 = Disable: No warning is given when the limit is reached
1 = Enable: A warning (see 33.65) is given when the limit is reached
2...15
Reserved
0000b...0011b
33.63
Value counter 2
source
Not selected
Motor speed
Other
33.64
Value counter 2
divider
0.001 ...
2147483.000
33.65
Value counter 2
warn message
Value counter 2
exceeded
Maintain motor
bearing
Description
Sets the limit for value counter 2.
With a positive limit, bit 5 of
(and a warning optionally generated) when the counter is
equal or greater than the limit.
With a negative limit, bit 5 of
(and a warning optionally generated) when the counter is
equal or smaller than the limit.
0 = Counter disabled.
Limit for value counter 2.
Configures value counter 2.
33.60
is reset. The warning (if enabled) also stays active until
is reset.
Value counter 2 configuration word.
Selects the signal to be monitored by value counter 2.
None (counter disabled).
01.01 Motor speed used
Source selection (see
page 152).
Defines a divisor for value counter 2. The value of the
monitored signal is divided by this value before integration.
Divisor for value counter 2.
Selects the optional warning message for value counter 2.
A88B Value counter
the control panel by choosing Menu – Settings – Edit texts.
A880 Motor
bearing.
33.01 Counter status
33.01 Counter status
(see page 156).
Terms and abbreviations
2. The message text can be edited on
Def/FbEq16
0
is set to 1
is set to 1
-
0000b
1 = 1
Not selected
0
1
on
-
1.000
-
Value
counter 2
exceeded
5
10