Hw Configuration - ABB ACQ80-04 Firmware Manual

Drives for water, standard control program
Hide thumbs Also See for ACQ80-04:
Table of Contents

Advertisement

162 Parameters
No.
Name/Value
Other [bit]
83.16
Cycles in cleaning
program
1...65535
83.20
Cleaning speed
step
0...3000 rpm
83.25
Time to cleaning
speed
0.000...60.000 s
83.26
Time to zero-speed
0.000...60.000 s
83.27
Cleaning on time
0.000...1000.000 s
83.28
Cleaning off time
0.000...1000.000 s
95

95 HW configuration

95.01
Supply voltage
Automatic / not
selected
380...415 V
Description
Source selection (see
Terms and abbreviations
Defines the number of cycles performed in cleaning program.
For example, 1 cycle = 1 forward + 1 reverse step.
Value range
Defines the speed/frequency step size in pump cleaning.
Cleaning speed step is same for positive and negative
directions.
Note: If you have disabled the negative rotation direction by
speed limits, the pump cleaning does not operate in the
negative direction.
Cleaning speed/frequency value.
Defines the time required for the drive to reach cleaning
speed set by parameter
Time
Defines the time required for the drive to reach zero speed
from the cleaning speed set by parameter
speed
step.
Time
Defines the pump cleaning time in a cycle when the drive is
running at cleaning speed set by
Time
Defines the cleaning off time when the drive stays at zero
speed between positive and negative pulses and after one
cleaning cycle before starting a new cleaning cycle.
Time
Various hardware-related settings.
Selects the supply voltage range. This parameter is used by
the drive to determine the nominal voltage of the supply
network. The parameter also affects the current ratings and
the DC voltage control functions of the drive.
WARNING! An incorrect setting may cause the motor
to rush uncontrollably.
Note: The selections shown depend on the hardware
of the drive. If only one voltage range is valid for the drive in
question, it is selected by default.
No voltage range selected. The drive will not start modulating
before a range is selected, unless parameter
voltage limits
is set to Enable, in which case the drive
estimates the supply voltage itself.
380...415 V
on page 64).
83.20 Cleaning speed
step.
83.20 Cleaning
83.20 Cleaning speed
95.02 Adaptive
Def/FbEq16
-
3
2400
1 = 1 rpm
3.000
1 = 1s
3.000
1 = 1s
10.000
step.
1 = 1s
5.000
1 = 1s
Automatic /
not selected
0
2

Hide quick links: