ABB ACS880 User Manual

ABB ACS880 User Manual

Prevention of unexpected start-up (option+q957) for acs880 multidrives
Hide thumbs Also See for ACS880:

Advertisement

OPTIONS FOR ABB DRIVES
Prevention of unexpected start-up (option
+Q957) for ACS880 multidrives
User's manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB ACS880

  • Page 1 — OPTIONS FOR ABB DRIVES Prevention of unexpected start-up (option +Q957) for ACS880 multidrives User's manual...
  • Page 3 Prevention of unexpected start-up (option +Q957) for ACS880 multidrives User's manual Table of contents 1. Safety instructions 4. Electrical installation 6. Start-up and acceptance test © 2019 ABB Oy. All Rights Reserved. 3AUA0000119894 Rev F EFFECTIVE: 2019-09-19...
  • Page 5: Table Of Contents

    Table of contents 5 Table of contents 1 Safety instructions Contents of this chapter ................Use of warnings and notes ..............Instructions for functional safety circuits ............Electrical safety precautions ..............2 Introduction to the manual Contents of this chapter ................Applicability ..................
  • Page 6 6 Table of contents Reporting problems and failures related to safety functions ........ 8 Maintenance Contents of this chapter ................Safety circuit maintenance ..............Proof test interval ................. Competence ..................Residual risk ..................Intentional misuse ................Decommissioning ................. 9 Technical data Contents of this chapter ................
  • Page 7: Safety Instructions

    Safety instructions 7 Safety instructions Contents of this chapter This chapter contains the safety instructions which you must obey when you install, operate and do maintenance on the safety functions of a drive. Use of warnings and notes Warnings tell you about conditions which can cause injury or death, or damage to the equipment.
  • Page 8: Electrical Safety Precautions

    8 Safety instructions Only a qualified electrician who has appropriate knowledge on functional, machine, and process safety is allowed to install, start up and maintain the safety circuit. All user-made changes are on the user's responsibility. WARNING! This safety function does not disconnect the voltage of the main and auxiliary circuits from the drive.
  • Page 9 Safety instructions 9 • Disconnect any dangerous external voltages from the control circuits. • After you disconnect power from the drive, always wait 5 minutes to let the intermediate circuit capacitors discharge before you continue. 3. Protect any other energized parts in the work location against contact. 4.
  • Page 11: Introduction To The Manual

    Exclusion of liability ABB is not responsible for the implementation, verification and validation of the overall safety system. It is the responsibility of the system integrator (or other party) who is responsible for the overall system and system safety.
  • Page 12: Quick Reference Guide For Taking A Safety Function Into Use

    Related manuals Manual Code Drive hardware Mechanical installation instructions for ACS880 multidrive cabinets 3AUA0000101764 Electrical planning instructions for ACS880 multidrive cabinets and modules 3AUA0000102324 Supply units ACS880-207 IGBT supply units hardware manual 3AUA0000130644 ACS880-307 (+A003) diode supply units hardware manual...
  • Page 13: Terms And Abbreviations

    You can find manuals and other product documents in PDF format on the Internet. See Document Library. For manuals not available in the Document library, contact your local ABB representative. For additional ABB safety information and solutions visit http://www.abb.com/safety. Terms and abbreviations Term Description Cat.
  • Page 15: Option Description

    Option description 15 Option description Contents of this chapter This chapter describes the option +Q957, prevention of unexpected start-up, and its settings. Overview The Prevention of unexpected start-up (POUS) function disables the control voltage of the power semiconductors of the drive (inverter) output stage. This prevents the drive from generating the torque required to rotate the motor.
  • Page 16: Operation Principle

    16 Option description Operation principle The figure shows a simplified operation principle. For a more detailed description, see the circuit diagrams delivered with the drive. -T22 -T22 -T22 -A41 -A41 -T11.x -T11.x XSTO XSTO -A65 -X51 B -X51 B -X52 B -X52 B XSTO XSTO...
  • Page 17: Fault Reaction Function

    (STO) signals are switched off or lost. Warning/Warning is the recommended setting. Note: ACS880 primary control program controls the inverter unit by default. There are dedicated control units for the supply and inverter units. Hardware settings Appropriate hardware settings have been preset at the factory for the safety function.
  • Page 19: Electrical Installation

    Electrical installation 19 Electrical installation Contents of this chapter This chapter describes the wiring of the safety option done at the factory and contains guidelines for making user connections (if any). Wiring The operating switch and the indication lamp for the POUS function are not factory-installed. The user must install and wire them to the inverter units on site.
  • Page 21: Use Of The Safety Function

    Use of the safety function 21 Use of the safety function Contents of this chapter This chapter describes the use of the safety function with factory default settings. Activating the safety function 1. Switch off the POUS switch. When the POUS is activated, the following indications are shown: •...
  • Page 23: Start-Up And Acceptance Test

    Start-up and acceptance test 23 Start-up and acceptance test Contents of this chapter This chapter describes the start-up, acceptance test procedure, and validation of the safety function. Validation of the safety functions You must do an acceptance test (validation) to validate the correct operation of safety functions.
  • Page 24: Acceptance Test Reports

    24 Start-up and acceptance test • you must sign and store the acceptance test report for further reference. ■ Acceptance test reports You must store the signed acceptance test reports in the logbook of the machine. The report must include, as required by the referred standards: •...
  • Page 25 Start-up and acceptance test 25 Action We recommend that you monitor these signals with the Drive composer PC tool: • 01.01 Motor speed used (rpm) • 01.02 Motor speed estimated (rpm) • 01.07 Motor current (A) • 01.10 Motor torque (%) •...
  • Page 27: Fault Tracing

    If STO hardware failure (5090) is generated, check STO wiring against the circuit diagrams. See inverter unit’s hardware manual for more information. For more fault tracing possibilities, see the hardware and firmware manuals of the drive. Reporting problems and failures related to safety functions Contact ABB.
  • Page 29: Maintenance

    If you change any wiring or component after the start-up or restore parameters to their factory default values: • Use only ABB-approved spare parts. • Register the change to the change log for the safety circuit. •...
  • Page 30: Competence

    30 Maintenance The person responsible for the design of the complete safety system should also note the Recommendation of Use CNB/M/11.050 published by the European co-ordination of Notified Bodies for Machinery concerning dual-channel safety-related systems with electromechanical outputs: • When the safety integrity requirement for the safety function is SIL 3 or PL e (cat. 3 or 4), the proof test for the function must be performed at least every month.
  • Page 31: Technical Data

    R10 and R11 and drives with R8i inverter modules: type B. ■ Safety block diagrams Each multidrives delivery is unique. If included in the customer order, ABB defines the safety block diagram for the safety function and delivers the diagram separately to the customer. ■...
  • Page 32: Fault Exclusions

    32 Technical data ■ Fault exclusions Fault exclusions (not considered in the calculations): • any short and open circuits in the cables of the safety circuit • any short and open circuits in the cabinet terminal blocks of the safety circuits. ■...
  • Page 33: Compliance With The European Machinery Directive

    Technical data 33 Compliance with the European Machinery Directive The drive is an electronic product which is covered by the European Low Voltage Directive. However, the drive internal safety function of this manual is in the scope of the Machinery Directive as a safety component.
  • Page 35: Further Information

    Product and service inquiries Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/searchchannels.
  • Page 36 3AUA0000119894F © 2019 ABB Oy. All Rights Reserved. Specifications subject to change without notice.

Table of Contents