376 Parameters
No.
Name/Value
Torque
Speed
Frequency
Position
50.08
FBA A actual 2 type
50.09
FBA A SW
transparent source
Not selected
Other
50.10
FBA A act1
transparent source
Not selected
Other
50.11
FBA A act2
transparent source
Not selected
Other
50.12
FBA A debug mode
Disable
Fast
50.13
FBA A control word
0.0.0.0 ...
FF.FF.FF.FF
50.14
FBA A reference 1
-2147483648 ...
2147483647
Description
01.10 Motor torque
is sent as actual value 1. The scaling is
defined by parameter
46.03 Torque
01.01 Motor speed used
scaling is defined by parameter
01.06 Output frequency
scaling is defined by parameter
Motor position is sent as actual value 1. See parameter
90.06 Motor position
scaled.
Selects the type/source and scaling of actual value 2
transmitted to the fieldbus network through fieldbus
adapter A.
See parameter
50.07 FBA A actual 1
Selects the source of the fieldbus status word when the
fieldbus adapter is set to a transparent communication
profile, for example, by its configuration parameters in group
51 FBA A
settings.
No source selected.
Source selection (see
Terms and abbreviations
152).
When parameter
50.07 FBA A actual 1 type
Transparent
or General, this parameter selects the source of
actual value 1 transmitted to the fieldbus network through
fieldbus adapter A.
No source selected.
Source selection (see
Terms and abbreviations
152).
When parameter
50.08 FBA A actual 2 type
Transparent
or General, this parameter selects the source of
actual value 2 transmitted to the fieldbus network through
fieldbus adapter A.
No source selected.
Source selection (see
Terms and abbreviations
152).
Enables the display of raw (unmodified) data received from
and sent to fieldbus adapter A in parameters 50.13...50.18.
This functionality should only be used for debugging.
Display of raw data from fieldbus adapter A disabled.
Display of raw data from fieldbus adapter A enabled.
Displays the raw (unmodified) control word sent by the
master (PLC) to fieldbus adapter A if debugging is enabled
by parameter
50.12 FBA A debug
This parameter is read-only.
Control word sent by master to fieldbus adapter A.
Displays raw (unmodified) reference REF1 sent by the
master (PLC) to fieldbus adapter A if debugging is enabled
by parameter
50.12 FBA A debug
This parameter is read-only.
Raw REF1 sent by master to fieldbus adapter A.
scaling.
is sent as actual value 1. The
46.01 Speed
scaling.
is sent as actual value 1. The
46.02 Frequency
type.
on page
is set to
on page
is set to
on page
mode.
mode.
Def/FbEq16
3
4
5
scaling.
6
General
Not selected
-
-
Not selected
-
-
Not selected
-
-
Disable
0
1
-
-
-
-