ABB ACS880 Firmware Manual page 379

Industrial drives, winder control program, option +n5000
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
Warning
50.33
FBA B comm loss
timeout
0.3 ... 6553.5 s
50.34
FBA B ref1 type
50.35
FBA B ref2 type
50.37
FBA B actual 1 type
50.38
FBA B actual 2 type
50.39
FBA B SW
transparent source
Not selected
Other
50.40
FBA B act1
transparent source
Not selected
Other
50.41
FBA B act2
transparent source
Not selected
Other
Description
Drive generates an
A7C2 FBA B communication
This occurs even though no control is expected from the
fieldbus.
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
Defines the time delay before the action defined by
parameter
50.32 FBA B comm loss func
starts when the communication link fails to update the
message.
As a rule of thumb, this parameter should be set to at least 3
times the transmit interval of the master.
Note: There is a 60-second boot-up delay immediately after
power-up. During the delay, communication break
monitoring is disabled (but communication itself can be
active).
Time delay.
Selects the type and scaling of reference 1 received from
fieldbus adapter B.
See parameter
50.04 FBA A ref1
Selects the type and scaling of reference 2 received from
fieldbus adapter B.
See parameter
50.04 FBA A ref1
Selects the type/source and scaling of actual value 1
transmitted to the fieldbus network through fieldbus
adapter B.
See parameter
50.07 FBA A actual 1
Selects the type/source and scaling of actual value 2
transmitted to the fieldbus network through fieldbus
adapter B.
See parameter
50.08 FBA A actual 2
Selects the source of the fieldbus status word when the
fieldbus adapter is set to a transparent communication
profile e.g. by its configuration parameters (group
settings).
No source selected.
Source selection (see
Terms and abbreviations
page 152).
When parameter
50.37 FBA B actual 1 type
Transparent
or General, this parameter selects the source of
actual value 1 transmitted to the fieldbus network through
fieldbus adapter B.
No source selected.
Source selection (see
Terms and abbreviations
page 152).
When parameter
50.38 FBA B actual 2 type
Transparent
or General, this parameter selects the source of
actual value 2 transmitted to the fieldbus network through
fieldbus adapter B.
No source selected.
Source selection (see
Terms and abbreviations
page 152).
Parameters 379
warning.
is taken. Time count
type.
type.
type.
type.
54 FBA B
on
is set to
on
is set to
on
Def/FbEq16
5
0.3 s
1 = 1 s
Auto
Auto
Auto
Auto
Not selected
-
-
Not selected
-
-
Not selected
-
-