ABB ACS880 Firmware Manual page 489

Industrial drives, winder control program, option +n5000
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
96.58
Approved
checksum 3
00000000h...
FFFFFFFFh
96.59
Approved
checksum 4
00000000h...
FFFFFFFFh
96.61
User data logger
status word
Bit
Name
0
Running
1
Triggered
2
Data
available
3
Configured
4...15
Reserved
0000b...1111b
96.63
User data logger
trigger
Off
On
Other [bit]
96.64
User data logger
start
Off
On
Other [bit]
96.65
Factory data logger
time level
500us
2ms
10ms
96.70
Disable adaptive
program
No
Yes
Description
Approved (reference) checksum 3.
Approved checksum 3.
Approved (reference) checksum 4.
Approved checksum 4.
Provides status information on the user data logger (see
page 567).
Description
1 = The user data logger is running. The bit is cleared after the post-
trigger time has passed.
1 = The user data logger has been triggered. The bit is cleared when the
logger is restarted.
1 = The user data logger contains data that can be read. Note that the bit
is not cleared because the data is saved to the memory unit.
1 = The user data logger has been configured. Note that the bit is not
cleared because the configuration data is saved to the memory unit.
User data logger status word.
Triggers, or selects a source that triggers, the user data
logger.
0.
1.
Source selection (see
Terms and abbreviations
152).
Starts, or selects a source that starts, the user data logger.
0.
1.
Source selection (see
Terms and abbreviations
152).
Selects the sampling interval for the factory data logger (see
page 566).
500 microseconds.
2 milliseconds.
10 milliseconds.
Enables/disables the adaptive program (if present).
See also section
Adaptive programming
Adaptive program enabled.
Adaptive program disabled.
Parameters 489
Def/FbEq16
0000h
-
0000h
-
0000b
1 = 1
Off
0
1
on page
-
Off
0
1
on page
-
500us
500
2000
10000
No
(page 67).
0
1