ABB ACS880 Firmware Manual page 596

Industrial drives, winder control program, option +n5000
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

596 Fault tracing
Code
Fault
(hex)
65B1
Reference source
parametrization
6681
EFB comm loss
Programmable fault:
58.14 Communication loss
action
6682
EFB config file
6683
EFB invalid
parameterization
6684
EFB load fault
6881
Text data overflow
6882
Text 32-bit table
overflow
6883
Text 64-bit table
overflow
6885
Text file overflow
7080
Option module comm
loss
7081
Control panel loss
Programmable fault:
Communication loss
action
7082
Ext I/O comm loss
Cause
A reference source is
simultaneously connected to
multiple parameters with
different units.
Communication break in
embedded fieldbus (EFB)
communication.
Embedded fieldbus (EFB)
configuration file could not be
read.
Embedded fieldbus (EFB)
parameter settings
inconsistent or not compatible
with selected protocol.
Embedded fieldbus (EFB)
protocol firmware could not be
loaded.
Version mismatch between
EFB protocol firmware and
drive firmware.
Internal fault.
Internal fault.
Internal fault.
Internal fault.
Communication between drive
and an option module is lost.
Control panel or PC tool
selected as active control
49.05
location for drive has ceased
communicating.
The I/O extension module
types specified by parameters
do not match the detected
configuration.
What to do
See
A6DA Reference source
parametrization
(page 575).
Check the status of the fieldbus master
(online/offline/error, etc.).
Check cable connections to the XD2D
connector on the control unit.
Contact your local ABB representative.
Check the settings in parameter group
Embedded
fieldbus.
Contact your local ABB representative.
Reset the fault. Contact your local ABB
representative if the fault persists.
Reset the fault. Contact your local ABB
representative if the fault persists.
Reset the fault. Contact your local ABB
representative if the fault persists.
Reset the fault. Contact your local ABB
representative if the fault persists.
See
A798 Encoder option comm loss
(page 577).
Check PC tool or control panel
connection.
Check control panel connector.
Disconnect and reconnect the control
panel.
Check the auxiliary code. The code
specifies the I/O port used as follows: 0:
Panel, 1: Fieldbus interface A, 2:
Fieldbus interface B, 3: Ethernet, 4:
D2D/EFB port)
Check the event log for an auxiliary code
(format XXYY YYYY). "XX" specifies the
number of the I/O extension module (01:
parameter group
14 I/O extension
module
1, 02:
15 I/O extension module
03:
16 I/O extension module
"YY YYYY" indicates the problem (see
actions for each code below).
58
2,
3).