Pfc Maintenance And Monitoring; Hw Configuration - ABB ACS580 Firmware Manual

General purpose drives, standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

No.
Name/Value
76.83
PFC interlock 3
76.84
PFC interlock 4
77
77 PFC maintenance
and monitoring
77.10
Runtime change
Done
Set any PFC run
time
Reset PFC1 run
time
Reset PFC2 run
time
Reset PFC3 run
time
Reset PFC4 run
time
77.11
Pump/fan 1 running
time
0.00...42949672.95
h
77.12
Pump/fan 2 running
time
77.13
Pump/fan 3 running
time
77.14
Pump/fan 4 running
time
95

95 HW configuration

95.01
Supply voltage
Automatic / not
selected
208...240 V
380...415 V
Description
See parameter
76.82 PFC interlock
See parameter
76.82 PFC interlock
PFC (Pump and fan control) maintenance and monitoring
parameters.
Enables the reset, or arbitrary setting, of
running time
...
77.14 Pump/fan 4 running
The parameter automatically reverts back to this value.
Enables the setting of
77.11 Pump/fan 1 running time
77.14 Pump/fan 4 running time
Resets parameter
77.11 Pump/fan 1 running
Resets parameter
77.12 Pump/fan 2 running
Resets parameter
77.13 Pump/fan 3 running
Resets parameter
77.14 Pump/fan 4 running
Running time counter of pump/fan 1. Can be set or reset by
parameter
77.10 Pump/fan 1 running
Time
See parameter
77.11 Pump/fan 1 running
See parameter
77.11 Pump/fan 1 running
See parameter
77.11 Pump/fan 1 running
Various hardware-related settings.
Selects the supply voltage range. This parameter is used by
the drive to determine the nominal voltage of the supply
network. The parameter also affects the current ratings and
the DC voltage control functions (trip and brake chopper
activation limits) of the drive.
WARNING! An incorrect setting may cause the motor
to rush uncontrollably, or the brake chopper or resistor
to overload.
Note: The selections shown depend on the hardware of the
drive. If only one voltage range is valid for the drive in
question, it is selected by default.
No voltage range selected. The drive will not start modulating
before a range is selected, unless parameter
voltage limits
is set to Enable, in which case the drive
estimates the supply voltage itself.
208...240 V
380...415 V
1.
1.
77.11 Pump/fan 1
time.
...
to an arbitrary value.
time.
time.
time.
time.
time.
time.
time.
time.
95.02 Adaptive
Parameters 305
Def/FbEq16
Available.
PFC motor is
available
Available.
PFC motor is
available
Done
0
1
2
3
4
5
0.00 h
1 = 1 h
0.00 h
0.00 h
0.00 h
Automatic /
not selected
0
1
2