312 Parameters
No.
Name/Value
0000...0111b
32.05
Supervision 1
function
Disabled
Low
High
Abs low
Abs high
Both
Abs both
32.06
Supervision 1 action
No action
Warning
Fault
32.07
Supervision 1 signal
Zero
Speed
Frequency
Current
Torque
DC voltage
Output power
AI1
AI2
Speed ref ramp in
Speed ref ramp out
Speed ref used
Torque ref used
Freq ref used
Process PID output
Process PID
feedback
Description
Signal supervision status word.
Selects the mode of signal supervision function 1.
Determines how the monitored signal (see parameter 32.07)
is compared to its lower and upper limits
respectively). The action to be taken when the condition is
fulfilled is selected by 32.06.
Signal supervision 1 not in use.
Action is taken whenever the signal falls below its lower limit. 1
Action is taken whenever the signal rises above its upper
limit.
Action is taken whenever the absolute value of the signal
falls below its (absolute) lower limit.
Action is taken whenever the absolute value of the signal
rises above its (absolute) upper limit.
Action is taken whenever the signal falls below its low limit or
rises above its high limit.
Action is taken whenever the absolute value of the signal
falls below its (absolute) low limit or rises above its
(absolute) high limit.
Selects the action the drive takes when the value monitored
by signal supervision 1 exceeds its limits.
Note: This parameter does not affect the status indicated by
32.01 Supervision
status.
No action taken.
A warning
(A8B0 Signal
The drive trips on
80B0 Signal
Selects the signal to be monitored by signal supervision
function 1.
None.
01.01 Motor speed used
01.06 Output frequency
01.07 Motor current
(page 156).
01.10 Motor torque
(page 156).
01.11 DC voltage
(page 156).
01.14 Output power
(page 157).
12.11 AI1 actual value
(page 196).
12.21 AI2 actual value
(page 198).
23.01 Speed ref ramp input
23.02 Speed ref ramp output
24.01 Used speed reference
26.02 Torque reference used
28.02 Frequency ref ramp output
40.01 Process PID output actual
40.02 Process PID feedback actual
(32.09
supervision) is generated.
supervision.
(page 156).
(page 156).
(page 257).
(page 257).
(page 263).
(page 279).
(page 286).
(page 341).
(page 341).
Def/FbEq16
1 = 1
Disabled
and
32.10
0
2
3
4
5
6
No action
0
1
2
Zero
0
1
3
4
6
7
8
9
10
18
19
20
21
22
24
25

Hide quick links: