570 Fault tracing
Code
Warning
(hex)
A491
External temperature
1
(Editable message text)
A492
External temperature
2
(Editable message text)
A497
Motor temperature 1
(Editable message text)
A498
Motor temperature 2
(Editable message text)
A499
Motor temperature 3
(Editable message text)
A4A0
Control board
temperature
A4A9
Cooling
A4B0
Excess temperature
Cause
Measured temperature 1 has
exceeded warning limit.
Measured temperature 2 has
exceeded warning limit.
The thermistor protection
module installed in slot 1
indicates overtemperature.
The thermistor protection
module installed in slot 2
indicates overtemperature.
The thermistor protection
module installed in slot 3
indicates overtemperature.
Control unit temperature is
excessive.
(none) Temperature above warning
limit
1 Thermistor broken
Drive module temperature is
excessive.
Power unit module
temperature is excessive.
What to do
Check the value of parameter
Measured temperature
1.
Check the cooling of the motor (or other
equipment whose temperature is being
measured).
Check the value of
35.13 Temperature 1
warning
limit.
Check the value of parameter
Measured temperature
2.
Check the cooling of the motor (or other
equipment whose temperature is being
measured).
Check the value of
35.23 Temperature 2
warning
limit.
Check the cooling of the motor.
Check the motor load and drive ratings.
Check the wiring of the temperature
sensor. Repair wiring if faulty.
Measure the resistance of the sensor.
Replace sensor if faulty.
Check the auxiliary code. See actions for
each code below.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Contact an ABB service representative
for control unit replacement.
Check ambient temperature. If it exceeds
40 °C (104 °F), ensure that load current
does not exceed derated load capacity of
drive. See appropriate Hardware manual.
Check drive module cooling air flow and
fan operation.
Check inside of cabinet and heatsink of
drive module for dust pick-up. Clean
whenever necessary.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
Check the auxiliary code (format XXXY
YYZZ). "Y YY" specifies through which
BCU control unit channel the fault was
received. "ZZ" specifies the location (1:
U-phase, 2: V-phase, 3: W-phase, 4: INT
board, 5: Brake chopper, 6: Air inlet, 7:
Power supply board, 8: du/dt filter (R8i)
or temperature switch (XT), 0FA:
Ambient temperature).
35.02
35.03