ABB ACS880 Firmware Manual page 595

Industrial drives, winder control program, option +n5000
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

Code
Fault
(hex)
64B0
Memory unit detached
64B1
Internal SSW fault
64B2
User set fault
64E1
Kernel overload
6581
Parameter system
65A1
FBA A parameter
conflict
65A2
FBA B parameter
conflict
Cause
000E Program corrupted or block
non-existent
0011 Program too large.
0012 Program is empty.
001C A non existing parameter or
block is used in the program.
001D Parameter type invalid for
selected pin.
001E Output to parameter failed
because the parameter was
write-protected.
0023 Program file incompatible with
current firmware version.
0024
Other –
The memory unit was
detached when the control unit
was powered.
Internal fault.
Loading of user parameter set
failed because
• requested set does not exist
• set is not compatible with
control program
• drive was switched off
during loading.
Operating system error.
Parameter load or save failed.
The drive does not have a
functionality requested by
PLC, or requested functionality
has not been activated.
The drive does not have a
functionality requested by
PLC, or requested functionality
has not been activated.
Fault tracing 595
What to do
Restore the template program or
download the program to the drive.
Remove blocks until the error stops.
Correct the program and download it to
the drive.
Edit the program to correct the parameter
reference, or to use an existing block.
Edit the program to correct the parameter
reference.
Check the parameter reference in the
program.
Check for other sources affecting the
target parameter.
Adapt the program to current block
library and firmware version.
Contact your local ABB representative,
quoting the auxiliary code.
Switch off the power to the control unit
and reinstall the memory unit.
In case the memory unit was not actually
removed when the fault occurred, check
that the memory unit is properly inserted
into its connector and its mounting screw
is tight. Reboot the control unit (using
parameter
96.08 Control board
by cycling power. If the problem persists,
contact your local ABB representative.
Reboot the control unit (using parameter
96.08 Control board
boot) or by cycling
power. If the problem persists, contact
your local ABB representative.
Ensure that a valid user parameter set
exists. Reload if uncertain.
Reboot the control unit (using parameter
96.08 Control board
boot) or by cycling
power. If the problem persists, contact
your local ABB representative.
Try forcing a save using parameter
Parameter save
manually. Retry.
Check PLC programming.
Check settings of parameter groups
Fieldbus adapter (FBA)
settings.
Check PLC programming.
Check settings of parameter groups
Fieldbus adapter (FBA)
settings.
boot) or
96.07
50
and
51 FBA A
50
and
54 FBA B