282 Parameters
No.
Name/Value
26.18
Torque ramp up
time
0.000 ... 60.000 s
26.19
Torque ramp down
time
0.000 ... 60.000 s
26.25
Torque additive 2
source
26.26
Force torque ref add
2 zero
Not selected
Selected
DI1
DI2
DI3
DI4
DI5
DI6
DIO1
DIO2
Other [bit]
26.41
Torque step
-300.0 ... 300.0%
Description
Defines the torque reference ramp-up time, i.e. the time for
the reference to increase from zero to nominal motor torque.
Torque reference ramp-up time.
Defines the torque reference ramp-down time, i.e. the time
for the reference to decrease from nominal motor torque to
zero.
Torque reference ramp-down time.
Selects the source of torque reference additive 2.
The value received from the selected source is added to the
torque reference after operating mode selection. Because of
this, the additive can be used in speed and torque modes.
Note: For safety reasons, the additive is not applied when
an emergency stop is active.
WARNING! If the additive exceeds the limits set by
parameters
25.11 Speed control min torque
25.12 Speed control max
be impossible. Make sure the additive is reduced or
removed when a ramp stop is required e.g. by using
parameter
26.26 Force torque ref add 2
See the control chain diagram on page 652.
For the selections, see parameter
Selects a source that forces torque reference additive 2 (see
parameter
26.25 Torque additive 2
0 = Normal operation
1 = Force torque reference additive 2 to zero.
0.
1.
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Digital input/output DIO1
Digital input/output DIO2
Source selection (see
Terms and abbreviations
page 152).
When enabled by parameter
adds an additional step to the torque reference.
Note: For safety reasons, the torque step is not applied
when an emergency stop is active.
WARNING! If the torque step exceeds the limits set
by parameters
25.11 Speed control min torque
25.12 Speed control max
impossible. Make sure the torque step is reduced or
removed when a ramp stop is required e.g. by using
parameter
26.42 Torque step
Torque step.
torque, a ramp stop may
zero.
26.11 Torque ref1
source) to zero.
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
(11.02 DIO delayed
status, bit 0).
(11.02 DIO delayed
status, bit 1).
on
26.42 Torque step
enable,
torque, a ramp stop may be
enable.
Def/FbEq16
0.000 s
100 = 1 s
0.000 s
100 = 1 s
Zero
and
source.
Not selected
0
1
2
3
4
5
6
7
10
11
-
0.0%
and
See par.
46.03