244 Parameters
No.
Name/Value
DI5
DI6
DIO1
DIO2
Other [bit]
21.06
Zero speed limit
0.00 ...
30000.00 rpm
21.07
Zero speed delay
Description
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Digital input/output DIO1
Digital input/output DIO2
Source selection (see
Terms and abbreviations
page 152).
Defines the zero speed limit. The motor is stopped along a
speed ramp (when ramped stop is selected) until the defined
zero speed limit is reached. After the zero speed delay, the
motor coasts to a stop.
Zero speed limit.
Defines the delay for the zero speed delay function. The
function is useful in applications where a smooth and quick
restarting is essential. During the delay, the drive knows the
rotor position accurately.
Without zero speed delay:
The drive receives a stop command and decelerates along
a ramp. When actual motor speed falls below the value of
parameter
21.06 Zero speed
stopped and the motor coasts to a standstill.
Speed
status, bit 4).
status, bit 5).
(11.02 DIO delayed
status, bit 0).
(11.02 DIO delayed
status, bit 1).
on
limit, inverter modulation is
Speed controller switched off:
Motor coasts to a stop.
Time
Def/FbEq16
7
8
11
12
-
30.00 rpm
See par.
46.01
0 ms