Hw Configuration - ABB ACS880 Firmware Manual

Dc/dc converter control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

142 Parameters
No.
Name/Value
195

195 HW configuration

195.01
Supply voltage
Not given
380 ... 415 V
440 ... 480 V
500 V
525 ... 600 V
660 ... 690 V
195.04
Control board supply
Internal 24V
External 24V
Redundant external
24V
195.09
Fuse switch control
No
Yes
195.14
Connected modules
Bit
0
1
0000h...FFFFh
Description
Various hardware-related settings.
Selects the supply voltage range. This parameter is used by
the control program to determine the nominal voltage of the
supply network.
No voltage defined.
380 ... 415 V.
440 ... 480 V.
500 V.
525 ... 600 V.
660 ... 690 V.
Specifies how the control unit of the DC/DC converter unit is
powered.
The control unit is powered from the power unit it is
connected to.
The control unit is powered from an external power supply.
Redundant supervision of 24 V signal. A warning
External power signal
supply is missing.
Activates communication to a xSFC charging controller.
This setting is intended for use with modules that are
connected to a DC bus through a DC switch/charging circuit
controlled by a charging controller.
The charging controller monitors the charging of the unit,
and sends an enable command when the charging has
finished. When the DC switch is opened, the charging
controller stops the unit.
For more information, see xSFC documentation.
Communication with xSFC disabled.
Communication with xSFC enabled.
Shows which power modules have been detected.
Single module = 0x0001,
two modules = 0x0003.
Name
Description
Module 1
1 = Module 1 has been detected.
Module 2
1 = Module 2 has been detected.
Power modules connected.
missing) is generated if the power
Def/FbEq16
Not given
0
2
3
4
5
6
External 24V
0
1
(AE5C
2
Yes
0
1
-
1 = 1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents