158 Parameters
No.
Name/Value
01.29
Speed change rate
-15000 ... 15000
rpm/s
01.30
Nominal torque
scale
0.000... N·m or lb·ft
01.31
Ambient
temperature
-32768 ... 32767 °C
or °F
01.32
Inverter GWh
regenerating
0...32767 GWh
01.33
Inverter MWh
regenerating
0...999 MWh
01.34
Inverter kWh
regenerating
0...999 kWh
01.35
Mot - regen energy
GWh
-32768...32767
GWh
01.36
Mot - regen energy
MWh
-999...999 MWh
01.37
Mot - regen energy
kWh
-999...999 kWh
01.61
Abs motor speed
used
0.00 ...
30000.00 rpm
Description
Rate of speed reference change after the speed ramp
generator.
See also parameters
31.32 Emergency ramp
31.33 Emergency ramp supervision
supervision
and
31.38 Ramp stop supervision
Rate of speed change.
Torque that corresponds to 100% of nominal motor torque.
The unit is selected by parameter
Note: This value is copied from parameter
nominal torque
if entered. Otherwise the value is calculated
from other motor data.
Nominal torque.
Measured temperature of incoming cooling air. The unit is
selected by parameter
96.16 Unit
Cooling air temperature.
Amount of energy that has passed through the drive
(towards the supply) in full gigawatt-hours. The minimum
value is zero.
Regenerative energy in GWh.
Amount of energy that has passed through the drive
(towards the supply) in full megawatt-hours. Whenever the
counter rolls over,
01.32 Inverter GWh regenerating
incremented.The minimum value is zero.
Regenerative energy in MWh.
Amount of energy that has passed through the drive
(towards the supply) in full kilowatt-hours. Whenever the
counter rolls over,
01.33 Inverter MWh regenerating
incremented.The minimum value is zero.
Regenerative energy in kWh.
Amount of net energy (motoring energy - regenerating
energy) that has passed through the drive in full gigawatt-
hours.
Energy balance in GWh.
Amount of net energy (motoring energy - regenerating
energy) that has passed through the drive in full megawatt-
hours. Whenever the counter rolls over,
energy GWh
is incremented or decremented.
Energy balance in MWh.
Amount of energy (motoring energy - regenerating energy)
that has passed through the drive in full kilowatt-hours.
Whenever the counter rolls over,
MWh
is incremented or decremented.
Energy balance in kWh.
Absolute value of
01.01 Motor speed
Measured or estimated motor speed.
supervision,
delay,
31.37 Ramp stop
delay.
96.16 Unit selection
99.12 Motor
selection.
is
is
01.35 Mot - regen
01.36 Mot - regen energy
used.
Def/FbEq16
-
1 = 1 rpm/s
-
1 = 100 unit
-
1 = 1°
-
1 = 1 GWh
-
1 = 1 MWh
-
10 = 1 kWh
-
1 = 1 GWh
-
1 = 1 MWh
-
10 = 1 kWh
-
See par.
46.01