ABB ACS880 Firmware Manual page 477

Industrial drives, winder control program, option +n5000
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
440...480 V
500 V
525...600 V
660...690 V
95.02
Adaptive voltage
limits
Disable
Enable
95.04
Control board
supply
Internal 24V
External 24V
Redundant external
24V
Description
440...480 V
500 V
525...600 V
660...690 V
Enables adaptive voltage limits.
Adaptive voltage limits can be used if, for example, an IGBT
supply unit is used to raise the DC voltage level. If the
communication between the inverter and the IGBT supply
unit is active
(95.20 HW options word
are related to the DC voltage reference transmitted to the
supply unit (94.20 DC voltage reference) assuming that the
reference is high enough. Otherwise, the limits are
calculated based on the measured DC voltage at the end of
the pre-charging sequence.
This function is also useful if the AC supply voltage to the
drive is high, as the warning levels are raised accordingly.
Adaptive voltage limits disabled.
Adaptive voltage limits enabled.
Specifies how the control unit of the drive is powered.
The drive control unit is powered from the drive power unit it
is connected to.
The drive control unit is powered from an external power
supply.
(Type BCU control units only) The drive control unit is
powered from two redundant external power supplies. The
loss of one of the supplies generates a warning
External power signal
missing).
Parameters 477
1), the voltage limits
(AFEC
Def/FbEq16
3
4
5
6
Disable
0
1
Internal
24V;
External 24V
(95.20
b4)
0
1
2

Hide quick links: