Standard Ai - ABB ACS880 Firmware Manual

Industrial drives, winder control program, option +n5000
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
11.59
Freq out 1 src max
-32768.000 ...
32767.000
11.60
Freq out 1 at src
min
0...16000 Hz
11.61
Freq out 1 at src
max
0...16000 Hz
11.81
DIO filter time
0.3...100.0 ms
12

12 Standard AI

12.01
AI tune
No action
AI1 min tune
AI1 max tune
AI2 min tune
AI2 max tune
12.03
AI supervision
function
No action
Fault
Warning
Description
Defines the real value of the signal (selected by parameter
11.55 Freq out 1 source
out 1 actual
value) that corresponds to the maximum value
of frequency output 1 (defined by parameter
1 at src
max). See parameter
Real signal value corresponding to maximum value of
frequency output 1.
Defines the minimum value of frequency output 1. See
diagrams at parameter
11.58 Freq out 1 src
Minimum value of frequency output 1.
Defines the maximum value of frequency output 1. See
diagrams at parameter
11.58 Freq out 1 src
Maximum value of frequency output 1.
Defines a filtering time for parameter
filtering time affects only the DIOs that are in input mode.
Filtering time for 11.01.
Configuration of standard analog inputs.
Triggers the analog input tuning function.
Connect the signal to the input and select the appropriate
tuning function.
AI tune is not activated.
Current analog input AI1 signal value is set as minimum
value of AI1 into parameter
back to
No action
automatically.
Current analog input AI1 signal value is set as maximum
value of AI1 into parameter
reverts back to
No action
Current analog input AI2 signal value is set as minimum
value of AI2 into parameter
back to
No action
automatically.
Current analog input AI2 signal value is set as maximum
value of AI2 into parameter
reverts back to
No action
Selects how the drive reacts when an analog input signal
moves out of the minimum and/or maximum limits specified
for the input.
The supervision applies a margin of 0.5 V or 1.0 mA to the
limits. For example, if the maximum limit for the input is
7.000 V, the maximum limit supervision activates at 7.500 V.
The inputs and the limits to be observed are selected by
parameter
12.04 AI supervision
Note: Analog input signal supervision is only active when
• the analog input is set as the source (using the
or
AI2 scaled
selection) in parameter 22.11, 22.12, 22.15,
22.17, 23.42, 26.11, 26.12, 26.16, 26.25, 28.11, 28.12,
30.21, 30.22, 40.16, 40.17, 40.50, 41.16, 41.17,
44.09, and
• is being used as the active source.
No action taken.
Drive trips on
80A0 AI
supervision.
Drive generates an
A8A0 AI supervision
and shown by parameter
11.61 Freq out
11.58 Freq out 1 src
min.
min.
11.01 DIO
12.17 AI1
min. The value reverts
12.18 AI1
max. The value
automatically.
12.27 AI2
min. The value reverts
12.28 AI2
max. The value
automatically.
selection.
warning.
Parameters 195
Def/FbEq16
1500.000
11.54 Freq
min.
1 = 1
0 Hz
1 = 1 Hz
16000 Hz
1 = 1 Hz
status. The
10.0 ms
10 = 1 ms
0
1
2
3
4
No action
AI1 scaled
41.50
or
0
1
2

Hide quick links: