ABB ACS880 Firmware Manual page 590

Industrial drives, winder control program, option +n5000
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

590 Fault tracing
Code
Fault
(hex)
3385
Autophasing
Motor cable overload
4000
4210
IGBT overtemperature Estimated drive IGBT
4290
Cooling
42F1
IGBT temperature
4310
Excess temperature
4380
Excess temperature
difference
4981
External temperature
1
(Editable message text)
Cause
Autophasing routine (see
section
Autophasing
on page
100) has failed.
Calculated motor cable
temperature has exceeded
warning limit.
temperature is excessive.
Drive module temperature is
excessive.
Drive IGBT temperature is
excessive.
Power unit module
temperature is excessive.
High temperature difference
between the IGBTs of different
phases.
Measured temperature 1 has
exceeded fault limit.
What to do
Try other autophasing modes (see
parameter
21.13 Autophasing
possible.
If the
Turning with Z-pulse
selected, check the zero pulse given by
the encoder.
Check that the motor ID run has been
successfully completed.
Clear parameter
98.15 Position offset
user.
Check that the encoder is not slipping on
the motor shaft.
Check that the motor is not already
turning when the autophasing routine
starts.
Check the setting of parameter
Motor
type.
Check the settings of parameters
and 35.62.
Check the dimensioning of the motor
cable in regard to required load.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
Check ambient temperature. If it exceeds
40 °C (104 °F), ensure that load current
does not exceed derated load capacity of
drive. See appropriate Hardware manual.
Check drive module cooling air flow and
fan operation.
Check inside of cabinet and heatsink of
drive module for dust pick-up. Clean
whenever necessary.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
See
A4B0 Excess temperature
570).
See
A4B1 Excess temperature
difference
(page 571).
Check the value of parameter
Measured temperature
1.
Check the cooling of the motor (or other
equipment whose temperature is being
measured).
Check the value of parameter
Temperature 1 fault
limit.
mode) if
mode is
99.03
35.61
(page
35.02
35.12