594 Fault tracing
Code
Fault
(hex)
5698
Unknown power unit
fault
6000
Internal SW error
6181
FPGA version
incompatible
6200
Checksum mismatch
Programmable fault:
Checksum action
6306
FBA A mapping file
6307
FBA B mapping file
6481
Task overload
6487
Stack overflow
64A1
Internal file load
64A2
Internal record load
64A3
Application loading
64A5
Licensing fault
64A6
Adaptive program
Cause
Unidentified power unit logic
fault.
Internal error.
Firmware and FPGA file
version in the power unit are
incompatible.
The calculated parameter
checksum does not match any
96.54
enabled reference checksum.
Fieldbus adapter A mapping
file read error.
Fieldbus adapter B mapping
file read error.
Internal fault.
Internal fault.
File read error.
Internal record load error.
Application file incompatible or
corrupted.
8006 Not enough memory for the
application.
8007 The application contains the
wrong library version.
800A The application contains an
unknown target (system)
library function.
Running the control program is
prevented either because a
restrictive license exists, or
because a required license is
missing.
Error running the adaptive
program.
000A Program corrupted or block
non-existent
000C Required block input missing
What to do
Check power unit logic and firmware
compatibility.
Contact your local ABB representative.
Contact your local ABB representative
quoting the auxiliary code.
Reboot the control unit (using parameter
96.08 Control board
boot) or by cycling
power. If the problem persists, contact
your local ABB representative.
See
A686 Checksum mismatch
573).
Contact your local ABB representative.
Contact your local ABB representative.
Reboot the control unit (using parameter
96.08 Control board
boot) or by cycling
power. If the problem persists, contact
your local ABB representative.
Reboot the control unit (using parameter
96.08 Control board
boot) or by cycling
power. If the problem persists, contact
your local ABB representative.
Reboot the control unit (using parameter
96.08 Control board
boot) or by cycling
power. If the problem persists, contact
your local ABB representative.
Contact your local ABB representative.
Check the auxiliary code. See actions for
each code below.
Record the auxiliary codes of all active
licensing faults and contact your product
vendor for further instructions.
Check the auxiliary code (format
XXXX YYYY). "XXXX" specifies the
number of the function block (0000 =
generic error). "YYYY" indicates the
problem (see actions for each code
below).
Restore the template program or
download the program to the drive.
Check the inputs of the block.
(page