634 Fieldbus control through a fieldbus adapter

Control word and Status word

The Control word is the principal means for controlling the drive from a fieldbus
system. It is sent by the fieldbus master station to the drive through the adapter
module. The drive switches between its states according to the bit-coded instructions
in the Control word, and returns status information to the master in the Status word.
For the ABB Drives communication profile, the contents of the Control word and the
Status word are detailed on pages
637
and
638
respectively. The drive states are
presented in the state diagram (page 639).
When a transparent communication profile is selected e.g. by parameter group
51
FBA A
settings, the control word received from the PLC is available in
06.03 FBA A
transparent control
word. The individual bits of the word can then be used for drive
control through bit pointer parameters. The source of the status word, for example
06.50 User status word
1, can be selected by
50.09 FBA A SW transparent
source.
Debugging the network words
If parameter
50.12 FBA A debug mode
is set to Fast, the Control word received from
the fieldbus is shown by parameter
50.13 FBA A control
word, and the Status word
transmitted to the fieldbus network by
50.16 FBA A status
word. This "raw" data is
very useful to determine if the fieldbus master is transmitting the correct data before
handing control to the fieldbus network.