ABB ACS880 Firmware Manual page 237

Industrial drives, winder control program, option +n5000
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
20.07
Ext2 start trigger
type
Edge
Level
20.08
Ext2 in1 source
20.09
Ext2 in2 source
20.10
Ext2 in3 source
20.11
Run enable stop
mode
Coast
Ramp
Torque limit
20.12
Run enable 1
source
Not selected
Selected
DI1
DI2
DI3
DI4
DI5
DI6
DIO1
DIO2
FBA A MCW bit 3
Description
Defines whether the start signal for external control location
EXT2 is edge-triggered or level-triggered.
Note: This parameter is only effective when parameter
20.06 Ext2 commands
is set to
In1 Start fwd; In2 Start rev
The start signal is edge-triggered.
The start signal is level-triggered.
Selects source 1 for parameter
For the available selections, see parameter
source.
Selects source 2 for parameter
For the available selections, see parameter
source.
Selects source 3 for parameter
For the available selections, see parameter
source.
Selects the way the motor is stopped when the run enable
signal switches off.
The source of the run enable signal is selected by parameter
20.12 Run enable 1
source.
Stop by switching off the output semiconductors of the drive.
The motor coasts to a stop.
WARNING! If a mechanical brake is used, ensure it
is safe to stop the drive by coasting.
Stop along the active deceleration ramp. See parameter
group
23 Speed reference ramp
Stop according to torque limits (parameters
30.20).
Selects the source of external run enable signal. If the run
enable signal is switched off, the drive does not start. If
already running, the drive stops according to the setting in
parameter
20.11 Run enable stop
1 = Run enable signal on.
Note: You can suppress the warning that indicates a missing
signal using parameter
20.30 Enable signals warning
function.
See also parameter
20.19 Enable start
0.
1.
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Digital input/output DIO1
Digital input/output DIO2
Control word bit 3 received through fieldbus interface A.
In1
Start,
In1 Start; In2
or
Control
panel.
20.06 Ext2
commands.
20.03 Ext1 in1
20.06 Ext2
commands.
20.03 Ext1 in1
20.06 Ext2
commands.
20.03 Ext1 in1
on page 257.
30.19
mode.
command.
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
(11.02 DIO delayed
status, bit 0).
(11.02 DIO delayed
status, bit 1).
Parameters 237
Def/FbEq16
Edge
Dir,
0
1
Not selected
Not selected
Not selected
Coast
(95.20
b10)
0
1
and
2
DIIL
(95.20
b10);
Selected
(95.20
b5);
DI5
(95.20
b10)
0
1
2
3
4
5
6
7
10
11
30