No.
Name/Value
Fault always
Warning
50.03
FBA A comm loss t
out
0.3 ... 6553.5 s
50.04
FBA A ref1 type
Auto
Transparent
General
Torque
Speed
Frequency
50.05
FBA A ref2 type
50.07
FBA A actual 1 type
Auto
Transparent
General
Description
Drive trips on
7510 FBA A
though no control is expected from the fieldbus.
Drive generates an
A7C1 FBA A communication
This occurs even though no control is expected from the
fieldbus.
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
Defines the time delay before the action defined by
parameter
50.02 FBA A comm loss func
starts when the communication link fails to update the
message.
As a rule of thumb, this parameter should be set to at least 3
times the transmit interval of the master.
Note: There is a 60-second boot-up delay immediately after
power-up. During the delay, communication break
monitoring is disabled (but communication itself can be
active).
Time delay.
Selects the type and scaling of reference 1 received from
fieldbus adapter A.
Note: Fieldbus-specific communication profiles may use
different scalings. For more information, see the manual of
the fieldbus adapter.
Type and scaling are chosen automatically according to
which reference chain (see settings Torque, Speed,
Frequency) the incoming reference is connected to. if the
reference is not connected to any chain, no scaling is
applied (as with setting Transparent).
No scaling is applied (the 16-bit scaling is 1 = 1 unit).
Generic reference with a scaling of 100 = 1 (i.e. integer and
two decimals).
The scaling is defined by parameter
The scaling is defined by parameter
The scaling is defined by parameter
scaling.
Selects the type and scaling of reference 2 received from
fieldbus adapter A.
See parameter
50.04 FBA A ref1
Selects the type/source and scaling of actual value 1
transmitted to the fieldbus network through fieldbus
adapter A.
Note: Fieldbus-specific communication profiles may use
different scalings. For more information, see the manual of
the fieldbus adapter.
Type/source and scaling follow the type of reference 1
selected by parameter
50.04 FBA A ref1
individual settings below for the sources and scalings.
The value selected by parameter
transparent source
is sent as actual value 1. No scaling is
applied (the 16-bit scaling is 1 = 1 unit).
The value selected by parameter
transparent source
is sent as actual value 1 with a 16-bit
scaling of 100 = 1 unit (i.e. integer and two decimals).
communication. This occurs even
warning.
is taken. Time count
46.03 Torque
46.01 Speed
46.02 Frequency
type.
type. See the
50.10 FBA A act1
50.10 FBA A act1
Parameters 375
Def/FbEq16
4
5
0.3 s
1 = 1 s
General
0
1
2
scaling.
3
scaling.
4
5
General
General
0
1
2