ABB ACS880 Firmware Manual page 197

Industrial drives, winder control program, option +n5000
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
12.12
AI1 scaled value
-32768.000 ...
32767.000
12.15
AI1 unit selection
V
mA
12.16
AI1 filter time
0.000 ... 30.000 s
12.17
AI1 min
-22.000 ... 22.000
mA or V
12.18
AI1 max
-22.000 ... 22.000
mA or V
Description
Displays value of analog input AI1 after scaling. See
parameters
12.19 AI1 scaled at AI1 min
scaled at AI1
max.
This parameter is read-only.
Scaled value of analog input AI1.
Selects the unit for readings and settings related to analog
input AI1.
Note: This setting must match the corresponding hardware
setting on the drive control unit (see the hardware manual of
the drive). Control board reboot (either by cycling the power
or through parameter
96.08 Control board
to validate any changes in the hardware settings.
Volts.
Milliamperes.
Defines the filter time constant for analog input AI1.
%
Unfiltered signal
100
63
Filtered signal
T
-t/T
O = I × (1 - e
)
I = filter input (step)
O = filter output
t = time
T = filter time constant
Note: The signal is also filtered due to the signal interface
hardware (approximately 0.25 ms time constant). This
cannot be changed by any parameter.
Filter time constant.
Defines the minimum site value for analog input AI1.
Set the value actually sent to the drive when the analog
signal from plant is wound to its minimum setting.
See also parameter
12.01 AI
Minimum value of AI1.
Defines the maximum site value for analog input AI1.
Set the value actually sent to the drive when the analog
signal from plant is wound to its maximum setting.
See also parameter
12.01 AI
Maximum value of AI1.
and
12.20 AI1
boot) is required
t
tune.
tune.
Parameters 197
Def/FbEq16
-
1 = 1
V
2
10
0.100 s
1000 = 1 s
0.000 mA or
V
1000 = 1 mA
or V
20.000 mA
or 10.000 V
1000 = 1 mA
or V