Code
Fault
(hex)
00 0001 Communication with module
00 0002 Module not found.
00 0003 Configuration of module failed.
00 0004 Configuration of module failed.
7083
Panel reference
conflict
7084
Panel/PC tool version
conflict
7085
Incompatible option
module
7121
Motor stall
Programmable fault:
Stall function
7181
Brake resistor
7183
BR excess
temperature
Cause
failed.
Use of saved control panel
reference in multiple control
modes attempted.
The current version of the
control panel and/or PC tool
does not support a function.
(For example, older panel
versions cannot be used as a
source of external reference.)
Option module not supported.
(For example, type Fxxx-xx-M
fieldbus adapter modules are
not supported.)
Motor is operating in stall
region because of e.g.
31.24
excessive load or insufficient
motor power.
Brake resistor broken or not
connected.
Brake resistor temperature has
exceeded fault limit defined by
parameter
43.11 Brake resistor
fault
limit.
Fault tracing 597
What to do
Check that the module is properly seated
in its slot.
Check that the module and the slot
connector is not damaged.
Try installing the module into another
slot.
Check the type and location settings of
the modules (parameters 14.01/14.02,
15.01/15.02
or 16.01/16.02).
Check that the module is properly seated
in its slot.
Check that the module and the slot
connector is not damaged.
Try installing the module into another
slot.
The control panel reference can only be
saved for one reference type at a time.
Consider the possibility of using a copied
reference instead of saved reference
(see the reference selection parameter).
Update control panel and/or PC tool.
Contact your local ABB representative if
necessary.
Check the auxiliary code. The code
specifies the interface to which the
unsupported module is connected:
1: Fieldbus interface A, 2: Fieldbus
interface B.
Replace the module with a supported
type.
Check motor load and drive ratings.
Check fault function parameters.
Check that a brake resistor has been
connected.
Check the condition of the brake resistor.
Check the dimensioning of the brake
resistor.
Stop drive. Let resistor cool down.
Check resistor overload protection
function settings (parameter group
Brake
chopper).
Check fault limit setting, parameter
Brake resistor fault
limit.
Check that braking cycle meets allowed
limits.
43