426 Parameters
No.
Name/Value
76.05
Count up enable
Not selected
Selected
Roll is not Full Yet
Other
76.06
Count down enable
Not selected
Selected
Roll is not Full Yet
Other
76.07
Hold diameter count
Not selected
Selected
Other
76.08
Core diameter
0.0...32767.0 mm
76.09
Full roll diameter
0.0...32767.0 mm
76.11
Reset estimated
diameter
Not selected
Description
Activates/deactivates the diameter up-count. In feeder
applications, disable the count by setting the parameter to
Not
selected.
Diameter up-count not activated.
Diameter up-count activated.
Inverted status of bit 0 (Roll end) of
word. Estimated diameter stops counting up when
Actual diameter
gets to the extremes: either greater than full
roll diameter (set with parameter
less than empty core (set with parameter
diameter).
Source selection (see
Terms and abbreviations
152).
Activates/deactivates the diameter down-count. In feeder
applications, disable the count by setting the parameter to
Not
selected.
Diameter down-count not activated.
Diameter down-count activated.
Inverted status of bit 0 (Roll end) of
word. Estimated diameter stops counting down when
Actual diameter
gets to the extremes: either greater than full
roll diameter (set with parameter
less than empty core (set with parameter
diameter).
Source selection (see
Terms and abbreviations
page 152).
Selects the digital signal source to hold actual diameter
counter.
See also section
Diameter hold
Hold diameter counter is not activated.
Hold diameter counter is activated.
Source selection (see
Terms and abbreviations
page 152).
Defines the core diameter (minimum actual diameter value).
Core diameter.
Defines the full roll diameter (maximum actual diameter
value).
Full roll diameter.
Selects the source to reset the
If parameter
74.05 Winding mode
• Winder, the diameter value is reset to the core diameter
• Unwinder, the diameter value is reset to the full roll
diameter.
Note: If parameter
76.01 Diameter calculation mode
set to Estimated, and if you use this diameter reset signal,
the control program forces the actual diameter signal to
76.61 Measured
diameter, ignoring any applied filter and/or
diameter hold settings.
No diameter reset.
09.01 Winder status
09.11
76.09 Full roll
diameter) or
76.08 Core
on page
09.01 Winder status
09.11
76.09 Full roll
diameter) or
76.08 Core
on
on page 49.
on
Estimated
diameter.
is set to:
is not
Def/FbEq16
Selected
0
1
2
-
Selected
0
1
2
-
Not selected
0
1
-
150.0 mm
10 = 1 mm
500.0 mm
10 = 1 mm
Not selected
0