598 Fault tracing
Code
Fault
(hex)
7184
Brake resistor wiring
7191
BC short circuit
7192
BC IGBT excess
temperature
71A2
Mechanical brake
closing failed
Programmable fault:
Brake fault function
71A3
Mechanical brake
opening failed
Programmable fault:
Brake fault function
Cause
Brake resistor short circuit or
brake chopper control fault.
Short circuit in brake chopper
IGBT.
Brake chopper IGBT
temperature has exceeded
internal fault limit.
Mechanical brake control fault.
Activated e.g. if brake
acknowledgement is not as
44.17
expected during brake closing.
Mechanical brake control fault.
Activated e.g. if brake
acknowledgement is not as
44.17
expected during brake
opening.
What to do
Check brake chopper and brake resistor
connection.
Ensure brake resistor is not damaged.
After correcting the cause of the fault,
reboot the control unit (using parameter
96.08 Control board
boot) or by cycling
power.
Ensure brake resistor is connected and
not damaged.
Check the electrical specifications of the
brake resistor against the Hardware
manual.
Replace brake chopper (if replaceable).
After correcting the cause of the fault,
reboot the control unit (using parameter
96.08 Control board
boot) or by cycling
power.
Let chopper cool down.
Check for excessive ambient
temperature.
Check for cooling fan failure.
Check for obstructions in the air flow.
Check the dimensioning and cooling of
the cabinet.
Check resistor overload protection
function settings (parameter group
Brake
chopper).
Check that braking cycle meets allowed
limits.
Check that drive supply AC voltage is not
excessive.
Check mechanical brake connection.
Check mechanical brake settings in
parameter group
44 Mechanical brake
control.
Check that acknowledgement signal
matches actual status of brake.
Check mechanical brake connection.
Check mechanical brake settings in
parameter group
44 Mechanical brake
control.
Check that acknowledgement signal
matches actual status of brake.
43

Hide quick links: