Generic Timer & Counter - ABB ACS880 Firmware Manual

Industrial drives, winder control program, option +n5000
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
33
33 Generic timer &
counter
33.01
Counter status
Bit
Name
0
On-time1
1
On-time2
2
Edge 1
3
Edge 2
4
Value 1
5
Value 2
6...15
Reserved
0000 000b ...
0011 1111b
33.10
On-time 1 actual
0...4294967295 s
33.11
On-time 1 warn limit
0...4294967295 s
33.12
On-time 1 function
Bit
Function
0
Counter mode
0 = Loop: When the limit is reached, the counter is reset. The counter status (bit 0 of
33.01) switches to 1 for one second. The warning (if enabled) stays active for at least
10 seconds.
1 = Saturate: When the limit is reached, the counter status (bit 0 of 33.01) switches to
1, and remains so until
33.10
1
Warning enable
0 = Disable: No warning is given when the limit is reached
1 = Enable: A warning (see 33.14) is given when the limit is reached
2...15
Reserved
0000b...0011b
33.13
On-time 1 source
False
Description
Configuration of maintenance timers/counters.
See also section
Maintenance timers and counters
127).
Displays the maintenance timer/counter status word,
indicating which maintenance timers/counters have
exceeded their limits.
This parameter is read-only.
Description
1 = On-time timer 1 has reached its preset limit.
1 = On-time timer 2 has reached its preset limit.
1 = Signal edge counter 1 has reached its preset limit.
1 = Signal edge counter 2 has reached its preset limit.
1 = Value counter 1 has reached its preset limit.
1 = Value counter 2 has reached its preset limit.
Maintenance time/counter status word.
Displays the actual present value of on-time timer 1.
The timer runs whenever the signal selected by parameter
33.13 On-time 1 source
When the timer exceeds the limit set by
warn
limit, bit 0 of
warning specified by
given if enabled by
The timer can be reset from the Drive composer PC tool, or
from the control panel by keeping Reset depressed for over
3 seconds.
Actual present value of on-time timer 1.
Sets the warning limit for on-time timer 1.
Warning limit for on-time timer 1.
Configures on-time timer 1.
33.10
is reset. The warning (if enabled) also stays active until
is reset.
On-time timer 1 configuration word.
Selects the signal to be monitored by on-time timer 1.
Constant 0 (timer disabled).
is on.
33.11 On-time 1
33.01 Counter status
is set to 1. The
33.14 On-time 1 warn message
33.12 On-time 1
function.
Parameters 315
Def/FbEq16
(page
-
1 = 1
-
is also
-
0 s
-
0000b
1 = 1
False
0