480 Parameters
No.
Name/Value
95.20
HW options word 1
Bit
Name
0
Supply frequency
60 Hz
1
Emergency stop
Cat 0
2
Emergency stop
Cat 1
3
RO2 for -07
cabinet cooling fan
4
Externally powered
control unit
5
DC supply switch
6
DOL motor switch 1 = Motor fan control active. Affects 10.24, 35.100, 35.103, 35.104.
7
Not used
8
Service switch
9
Output contactor
10
Brake resistor, sine
filter, IP54 fan
11
Not used
12
Reserved
13
du/dt filter
activation
14
DOL fan activation 1 = The inverter unit consists of frame R8i modules with direct-on-line
15
INU-ISU
communication
0000h...FFFFh
Description
Specifies hardware-related options that require differentiated
parameter defaults. Activating a bit in this parameter makes
the necessary changes in other parameters – for example,
activating an emergency stop option reserves a digital input.
In many cases, the differentiated parameters will also be
write-protected.
This parameter, as well as the changes in other parameters
implemented by it, are not affected by a parameter restore.
WARNING! After switching any bits in this work,
recheck the values of the affected parameters.
Information
0 = 50 Hz; 1 = 60 Hz. Affects parameters 11.45, 11.59, 12.20, 13.18,
30.11, 30.12, 30.13, 30.14, 31.26, 31.27, 40.15, 40.37, 41.15, 41.37,
46.01, 46.02.
1 = Emergency stop, Category 0, without FSO module. Affects 21.04,
21.05, 23.11.
1 = Emergency stop, Category 1, without FSO module. Affects 10.24,
21.04, 21.05, 23.11.
1 = Control of cabinet cooling fan (used only with specific ACS880-07
hardware). Affects 10.27, 10.28, 10.29.
1 = Control unit powered externally. Affects 95.04. (Visible only with a
ZCU control unit)
1 = DC switch monitoring active. Affects 20.12, 31.03, 95.08. (Visible
only with a ZCU control unit)
1 = Service switch connected. Affects 31.01, 31.02.
1 = Output contactor present. Affects 10.24, 20.12.
1 = Status (e.g. thermal) switches connected to DIIL input. Affects
20.11, 20.12.
1 = Active: A du/dt filter is connected to the drive/inverter output.
Note: This bit is to be left at 0 if the drive/inverter module is equipped
with internal du/dt filtering (for example, frame R8i inverter modules
with option +E205).
cooling fans (option +C188). Disables fan feedback monitoring and
changes fan control to ON/OFF type.
*1 = IGBT supply unit control by inverter unit is active. Makes several
parameters visible in groups 01, 05, 06, 07, 30, 31, 60, 61,
Hardware options configuration word.
Def/FbEq16
-
62
and 96.
1 = 1