328 Parameters
No.
Name/Value
35.22
Temperature 2 fault
limit
-60 ... 1000 °C or
-76...1832 °F
35.23
Temperature 2
warning limit
-60 ... 5000 °C or
-76...9032 °F
35.24
Temperature 2 AI
source
Not selected
AI1 actual value
AI2 actual value
Other
35.30
FPTC configuration
word
Bit
Name
0
Module in slot 1
1
Disable slot 1 warning
2
Module in slot 2
3
Disable slot 2 warning
4
Module in slot 3
5
Disable slot 3 warning
6...15
Reserved
0000 0000b ...
0011 1111b
Description
Defines the fault limit for temperature monitoring function 2.
When measured temperature 2 exceeds the limit, the drive
trips on fault
4982 External temperature
The unit is selected by parameter
Note: With a PTC sensor, the unit is ohms.
Fault limit for temperature monitoring function 2.
Defines the warning limit for temperature monitoring
function 2. When measured temperature 2 exceeds the limit,
a warning
(A492 External temperature
The unit is selected by parameter
Note: With a PTC sensor, the unit is ohms.
Warning limit for temperature monitoring function 2.
Selects the input for parameter
selections
KTY84 analog
Pt100 analog
I/O,
3 x Pt100 analog I/O
temperature.
None.
Analog input AI1 on the control unit.
Analog input AI2 on the control unit.
Source selection (see
Terms and abbreviations
152).
Activates FPTC-xx thermistor protection modules installed
on the control unit of the drive. Using this word, it is also
possible to suppress the warnings (but not faults) from each
module.
Description
1 = Yes: Module installed in slot 1.
1 = Yes: Warnings from the module in slot 1 suppressed.
1 = Yes: Module installed in slot 2.
1 = Yes: Warnings from the module in slot 2 suppressed.
1 = Yes: Module installed in slot 3.
1 = Yes: Warnings from the module in slot 3 suppressed.
FPTC-xx module configuration word.
2.
96.16 Unit
selection.
2) is generated.
96.16 Unit
selection.
35.21 Temperature 2
I/O,
1 x Pt100 analog
I/O,
and
Direct
on page
Def/FbEq16
130 °C or
266 °F
1 = 1 unit
110 °C or
230 °F
1 = 1 unit
source,
Not selected
2 x
0
1
2
-
0000 0000b
1 = 1