4.7 Test Run

Jog Operation: FJOG/RJOG

Digital inputs programmed as Forward Jog (H1-
will be Jog inputs that do not require a run command. Closing the terminal set for Forward
Jog input will cause the drive to ramp to the Jog Frequency Reference (d1-17) in the forward
direction. The Reverse Jog will cause the same action in the reverse direction. The Forward
Jog and Reverse Jog can be set independently.

Jog Operation Parameters

No.
Name
Jog Frequency
d1-17
Reference

Selections for Digital Input Terminals S1 to S7 (H1-01 to H1-07)

Setting
12
FJOG Command (ON: rotates forward at the Jog frequency set to d1-17)
13
RJOG Command (ON: rotates in reverse at the Jog frequency set to d1-17)

Connection Example for the Jog Function

In this example, H1-07 = 12 and d1-17 = 6.0 Hz.
Figure 4.30
Three-Phase 200 Vac
(400 Vac)
166
Frequency reference when: "Jog Frequency Reference" is
selected via multi-function input terminals. "Jog Frequency
Reference" has priority over "Multi-Step Speed Reference 1 to
16." Parameter d1-17 is also the reference for the JOG key on
the digital operator, and the multi-function inputs "Forward
Jog" and "Reverse Jog."
Figure 4.30 Jog Command from External Terminals
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
= 12) and Reverse Jog (H1-
Description
Name
Drive
U/T1
R/L1
V/T2
S/L2
W/T3
T/L3
S7 (FJ0G)
SC
= 13)
Setting
Default
Range
Setting
0.00 to
6.00 Hz
400.00
M