YASKAWA V1000 Series Installation & Start-Up Manual page 293

Compact vector control drive
Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

<2> The motor capacity (kW) refers to a Yaskawa 4-pole motor. The rated output current of the drive output amps
should be equal to or greater than the motor rated current.
<3> Input current rating varies depending on the power supply transformer, input reactor, wiring connections, and
power supply impedance.
<4> Rated motor capacity is calculated with a rated output voltage of 220 V.
<5> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<7> Carrier frequency is set to 8 kHz. Current derating is required in order to raise the carrier frequency.
Note: Differences between Heavy Duty (HD) ratings and Normal Duty (ND)ratings for the drive
include rated input and output current, overload capacity, carrier frequency, current limit, and
maximum output frequency. Set parameter C6-01 to "0" for HD or "1" for ND (defult).
Note: CIMR-V BA0018 is available with a Heavy Duty rating only.
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
A.2 Single/Three-Phase 200 V Class Drive
A
293