Multiple Drive Installation

When installing multiple drives into the same enclosure panel, mount the drives according to
Figure
2.2. When mounting drives with a minimum side-by-side clearance of 2 mm
according to
Figure
2.3, derating must be considered and parameter L8-35 must be set.
Refer to Parameter List on page
Figure 2.3
B
A
2 mm
A – Line up the tops of the drives.
B – 30 mm minimum
Figure 2.3 Space Between Drives (Side-by-Side Mounting)
Note: When installing drives of different sizes into the same enclosure panel, the tops of the drives
should line up. Leave space between the top and bottom of stacked drives for cooling fan
replacement if required. Using this method, it is possible to replace the cooling fans later.
NOTICE: When drives with IP20/NEMA Type 1 enclosure are mounted side by side, the top covers of all
units must be removed as shown in the figure below.
Figure 2.4
Figure 2.4 IP20/NEMA 1 Side-by-Side Mounting in Enclosure